Product dimensions
(762cm) width |
height
Cabinet dimensions
30” (76.2cm) min. base cabinet is required. If cabinet has a drawer, a 3” (75cm) depth clearance from the countertop to the top of the drawer (or other obstruction) in the base cabinet is required.
Before you start...
Proper installation is your responsibility. Make sure you have everything for correct installation. It is the responsibility of the installer to comply with the installation clearances specified on the serial/rating plate. The serial/rating plate is found on the bottom of the cooktop.
Cooktop installed over oven installation: Cooktop models KECC500W, KECC500B, YKECC500B and YKECC500W can be installed over oven models KEBNl OOY, KEBNlO7B and RB262PXA.
Check location where cooktop will be installed. The location should be away from strong draft areas, such as windows, doors and strong heating vents or fans. The cooktop should be located for convenient use in the kitchen.
Important:
Observe all governing codes and ordinances.
Failure to meet governing codes and ordinances could lead to fire or electrical shock.
Countertop opening dimensions that are shown must be used. Given dimensions are minimum clearances and provide required 0” (Ocm) clearance.
New installations
| 30” | (76.2cm) | min. cabinet |
| above | cooktop | |
For | minimum |
| 4, |
clearances,f |
| 13Lk+ | |
see | Note.* |
| max. upper |
| cabinet | ||
|
|
| |
16” (45.7cm) | I |
|
|
countertop.
25” | (63.5cm) | (30cm) | or | |
more | above | |||
countertop | ||||
depth | the floor | |||
|
| line. |
|
24” (61cm) lower cabmet depth
‘/
/
min.
Note: 24” (61cm) min. clearance rf bottom of wood or metal cabinet is protected by not less than l/4” (O&m) flame retardant millboard covered with not less than No. 28 MSG sheet steel, 0.015” (0.04cm) stainless steel, or 0.024”(0.06cm)
’aluminum or 0.020” (OJXcm) copper.
30” (76.2cm) min. clearance between top of cooking platform and bottom of unprotected wood or metal cabinet.
Replacement installations - Be sure that front edge of cooktop is at least
A
When installing cooktop over a built- under oven, Do Not fasten cooktop to countertop with clamps. Cooktop then will be easy to remove if servicing is ever necessary.
ALL OPENINGS IN THE WALL OR FLOOR WHERE THE COOKTOP IS TO BE INSTALLED MUST BE SEALED.
Electrical Shock Hazard
It is the customer’s responsibility: l To contact a qualified electrical
installer.
l To assure that the electrical installation is adequate and in conformance with National Electrical Code, ANSVNFPA 70 - latest edition**, or Canadian Electrical Code, C22.1 - 1982 and C22.2 No. 01982 (or latest edition)*‘* and all local codes and ordinances.
Cutout dimensions
-Minimum distance
to nearest left side and rear combustible surface above countertop
Failure to do so could result in electrical shock or other personal injury.
Personal Injury Hazard Cabinet storage above the cooking surface should be avoided. If cabinets are already installed, reduce the hazard of reaching over a heated cooking surface by installing a range hood.
The range hood should extend a minimum of 5 inches out from the bottom of the cabinets.
Reaching over a heated cooking surface could result in a serious burn.
Copies of the standards listed may be obtained from:
**National Fire Protection Association Batterymarch Park
Quincy, Massachusetts 02269
***Canadian Standard Association 178 Rexdale Boulevard
Rexdale, (Toronto ), Ontario M9W 1R3