1. INTRODUCTION

As the world leader in the development and application of high technology ceramic/silica materials, Kyocera offers a wide range of highly efficient and reliable crystalline silicon solar photovoltaic (PV) power modules. Kyocera began to extensively research PV technology in 1975 and commenced manufacturing operations in 1978. Since then, Kyocera has supplied millions of cells and modules throughout the world. With years of experience and state-of-the-art technology, Kyocera provides the highest quality PV power modules in a range of sizes designed to meet the requirements of the most demanding energy and power users worldwide.

2. APPLICATIONS

KDxxxGX-LPx series modules are a reliable, virtually maintenance-free direct current (DC) power source, designed to operate at the highest level of efficiency.

KDxxxGX-LPx series modules are ideal for remote home, water pumping, utility-tied, telecommunications and many other applications either with or without using storage batteries.

3. WARNINGS & SAFETY

PV modules generate electricity when exposed to light. Arrays of many modules can cause lethal shock and burn hazards. Only authorized and trained personnel should have access to these modules. To reduce the risk of electrical shock or burns, modules may be covered with an opaque material during installation. Do not touch live terminals with bare hands. Use insulated tools for electrical connections. Do not use these modules for solar concentration.

PERMIT

Before installing your PV system, contact local authorities to determine the necessary permits, installation and inspection requirements.

INSTALLATION AND OPERATION

Systems should be installed by qualified personnel only. The system involves electricity, and can be dangerous if the personnel are not familiar with the appropriate safety procedures.

Do not step on the module.

Although KDxxxGX-LPxseries modules are quite durable, the glass can be broken (and the module will no longer work properly) if it is dropped or hit by tools or other objects.

The module frame is made of anodized aluminum, and therefore corrosion can occur if the module is subject to a salt-water environment and is in contact with another type of metal (electrolytic corrosion). If required, PVC or stainless steel washers can be placed between PV module frame and support structure to prevent this type of corrosion.

KDxxxGX-LPxseries module frame(s) must be attached to a support structure by one of the methods described in Section 6, Installing KDxxxGX-LPxseries module(s).

Module support structures to be used to support

KDxxxGX-LPxseries module(s) should be wind rated and approved by the appropriate local and civil codes prior to installation.

Do not expose the back of the module to direct sunlight

In Canada installation shall be in accordance with CSA C22.1, Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1.

When handle the modules, DO NOT HOLD THEM BY

SUPPORTING ONLY ONE SIDE OF THE LONG FRAME BECAUSE IT CAN CAUSE SEPARATION OF THE GLASS AND FRAME.

CAUTION

FIRE RATING

In case of roof installation, PV module assembly shall be mounted on a fire resistant roof covering rated for the application. KDxxxGX-LPxseries modules are comprised of a glass front surface, polyethylene terephthalate (PET) backsheet with a Class C fire rating.

GROUNDING

Refer to “Grounding” section.

BATTERY

When PV modules are used to charge batteries, the battery must be installed in a manner, which will ensure the performance of the system and the safety of its users.

Follow the battery manufacturers safety guidelines concerning installation, operation and maintenance recommendations. In general, the battery (or battery bank) should be kept away from people and animals. Select a battery site that is protected from sunlight, rain, snow, debris, and is well ventilated. Most batteries generate hydrogen gas when charging, which can be explosive. Do not light matches or create sparks near the battery bank. When a battery is installed outdoors, it should be placed in an insulated and ventilated battery case specifically designed for this purpose.

4. SITE SELECTION

In most applications, KDxxxGX-LPxseries modules should be installed in a location where they will receive maximum sunlight throughout the year. In the Northern Hemisphere,