
TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM
Note: Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in the
“ON” position. Important: Valve system troubleshooting should only be accomplished by a qualified service technician.
| SYMPTOM |
| POSSIBLE CAUSES |
|
| CORRECTIVE ACTION |
|
|
|
|
|
|
| ||||
1) Spark igniter will not light | A. Electrode wire (at piezo igniter) not pushed completely | • Check connection |
|
| ||||
pilot after repeated triggering of | on. |
|
|
|
|
|
| |
igniter button. |
|
|
|
|
|
|
| |
B. | Piezo igniter is defective | • | Replace piezo igniter |
|
| |||
WARNING: IF THE PILOT WILL |
|
| ||||||
|
|
|
|
|
|
| ||
C. Defective or misaligned electrode at pilot (spark at | • Using a match, light pilot. If pilot lights, turn off pilot and trigger the igniter |
| ||||||
NOTLIGHTAFTERONEMINUTE |
| |||||||
electrode) | button again. If pilot lights, an improper gas mixture caused the bad lighting |
| ||||||
OF ATTEMPTING, WAIT FOR AT |
| |||||||
|
| and a longer purge period is recommended. If pilot will not light – check gap at |
| |||||
LEAST FIVE MINUTES FOR GAS |
|
|
| |||||
|
| electrode and pilot – It should be between 1/8” and 3/16.” If the gap is out of this |
| |||||
TO CLEAR BEFORE ATTEMPT- |
|
|
| |||||
|
| range, adjust the gap or replace the pilot assembly. See Page 11, Figure 25. |
| |||||
ING AGAIN. |
|
|
| |||||
|
|
|
|
|
|
| ||
|
| D. Incorrect lighting procedure | • Carefully follow the lighting instructions on Pages 15 &16 or as found in the |
| ||||
|
|
|
| insert control compartment. |
|
| ||
|
| E. Gas supply problem | • | Check for multiple gas |
| |||
|
|
|
| pressure. It should be within the limits as marked on the rating plate. |
|
| ||
|
|
|
|
|
| |||
|
| F. Pilot orifice plugged | • Clean or replace pilot orifice |
|
| |||
|
|
|
|
| ||||
2) Pilot will not stay lit after | A. Thermocouple is not firmly connected to control valve | • Check connection at valve |
|
| ||||
carefully following the lighting |
|
|
|
|
|
|
| |
B. Pilot flame is not directed to top of thermocouple | • Ensure thermocouple is fully inserted into pilot assembly. Clean and/or adjust |
| ||||||
instructions. |
| |||||||
|
|
|
| pilot for maximum flame impingement on thermocouple if necessary. |
|
| ||
|
| C. Thermocouple is defective. The millivolt production | • | Replace thermocouple |
|
| ||
|
| should be a minimum of 14 MV with pilot only. |
|
|
|
|
| |
3) | Pilot flame stays lit, but | A. Burner control switch (off/on switch, wall thermostat | • Turn burner off/on switch on and/or refer to instructions provided with optional |
| ||||
main burner will not light | or remote control) is in “OFF” position; or thermostat (if | thermostat or remote control, if applicable. |
|
| ||||
(valve pilot/off/on knob is in | installed) is set to a temperature setting that is too low. |
|
|
|
|
| ||
ON position, off/on switch, wall |
|
|
|
|
|
|
| |
B. Electrical wiring is damaged or poorly connected or | • Check wall switch and wires for proper connections. Refer to Millivolt Wiring |
| ||||||
thermostat or remote control is |
| |||||||
set to ON). | remote switch is defective. | Diagram(Page12,Figure28). Jumpthewireacrossterminalsatthewallswitch, |
| |||||
|
|
|
| if the burner comes on, replace the defective wall switch. If okay, jumper the |
| |||
Read important note below. |
|
| wires across the wall switch wires at the valve. If the burner comes on, wires |
| ||||
| IMPORTANT NOTE: If an |
|
| are faulty or connections are bad. |
|
| ||
| C. | One of the following components may be defective: | • | Refer to Millivolt Wiring Diagram (Page 12, Figure 28). Electrically bypass |
| |||
| optional Remote Switch* |
| ||||||
| burner control switch, thermostat, vent spill switch, or | components one at a time and replace defective item. |
|
| ||||
| is used for burner opera- |
|
| |||||
| thermopile. Thermopile: Millivolt production should be a |
|
|
|
|
| ||
| tion and if the standard |
|
|
|
|
| ||
| minimum of 325 MV with pilot only. |
|
|
|
|
| ||
| burner OFF/ON switch is |
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
| still installed on appli- | D. Thermopile may not be generating sufficient mil- | • Check thermopile with millivolt meter. Take reading at thermopile terminals |
| ||||
| ance, it must be in the |
| ||||||
|
| livolts | of gas valve. It should read 325 millivolts minimum with optional wall switch |
| ||||
| "OFF" position. |
|
| |||||
|
|
| “OFF.” Replace faulty thermopile if reading is below specified minimum. |
| ||||
|
|
|
|
| ||||
|
|
|
|
|
|
| ||
|
| E. | Plugged burner orifice | • Check burner orifice for blockage and remove. |
|
| ||
|
|
|
|
| ||||
|
| F. OFF/ON Switch & Remote Switch* are in the "ON" | • When turning on the burner using a Remote Switch,* ensure that the |
| ||||
|
|
| position resulting in excessive resistance | standard OFF/ON Switch is in the "OFF" position. If both switches are in |
| |||
|
|
|
| the ON position, it may result in excessive resistance (& millivolt drainage) |
| |||
|
|
|
| and the burner may not come on. |
|
| ||
4) | Frequentpilot/burneroutage | A. Pilot flame may be too low or blowing (high) causing | • Clean and/or adjust pilot flame for maximum flame impingement on thermo- |
| ||||
problem | the pilot/valve safety to drop out. | couple. See Page 11, Figure 25. |
|
| ||||
5) Main burner stays lit for up | A. Vent is blocked; flue gas is “spilling,” which activates | • Examine venting system for blockage. Remove any blockage. |
|
| ||||
to 10 minutes and then shuts off, | the spill switch and shuts down the burner. |
|
|
|
|
| ||
pilot flame remains lit. |
|
|
|
|
|
|
| |
B. The house is negatively pressurized resulting in spill | • Open a window to see if the problem is corrected. |
|
| |||||
|
|
|
| |||||
|
| switch activation. |
|
|
|
|
| |
|
|
|
|
|
| |||
6) | Smell of gas | A. Pilot, gas supply system, or pilot & burner adjustment | • WARNING: NEVER USE AN OPEN FLAME TO CHECK FOR LEAKS. |
|
| |||
|
| screwsonvalvemaybeleaking. FOLLOW INSTRUCTIONS | After the gas company or fire department has given clearance to |
| ||||
|
| ON THE COVER OF THIS MANUAL | dwelling, have a qualified technician test all gas joints from the gas meter to |
| ||||
|
|
|
| the gas heater regulator for leaks using a gas leak test solution (also referred |
| |||
|
|
|
| to as bubble leak solution). |
|
| ||
7) A thin coating of black soot | A. | Burner primary air inlet is restricted or blocked | • Ensure all openings (fresh air inlets) in the insert are free from dust and debris. |
| ||||
forms on the window. |
|
| Recheck these areas periodically. |
|
| |||
Note: See Page 5, Glass Clean- | B. | Flames make contact with logs or other surfaces | • Ensure ceramic logs are in their correct positions. |
|
| |||
ing. |
| C. | Improper venting | • | Check for flue blockage, disconnected flue, improper installation. | Make |
| |
|
|
| ||||||
|
|
|
| appropriate corrections. |
|
| ||
|
|
|
|
| ||||
8) | A white coating forms on | A. Residues/impurities being burned off or impurities in | • Follow cleaning guidelines outlined in the MAINTENANCE section of this |
| ||||
windows,logs,and/orinsidewalls | the fuel | manual. |
|
| ||||
of firebox. |
|
|
|
|
|
|
| |
*Optional Remote Switch kits: wall switch, wall thermostatNOTE:or remoteDIAGRAMScontrol& ILLUSTRATIONS. | ARE NOT TO SCALE. |
| 19 |