G43UF / Page 14
BLOWER/WATTS DATA
G43UF−48C−090 PERFORMANCE (Less Filter)
External Static Air Volume / Watts at Different Blower Speeds
External
Static
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2180 1030 930 1835 865 790 1520 715 630 1280 605 510
0.10 25 2135 1005 885 1825 860 750 1510 710 610 1275 600 495
0.20 50 2085 985 840 1810 855 720 1505 710 580 1270 600 475
0.30 75 2030 955 800 1775 835 685 1500 705 565 1265 595 460
0.40 100 1940 915 760 1735 820 650 1480 700 535 1250 590 440
0.50 125 1865 880 725 1660 785 600 1430 675 505 1215 575 425
0.60 150 1740 820 670 1590 750 575 1380 650 475 1175 555 410
0.70 175 1645 775 640 1475 695 520 1290 610 450 1105 520 375
0.80 200 1540 725 600 1340 630 465 1175 555 405 1020 480 355
0.90 225 1335 630 540 1170 555 440 1070 505 375 950 450 330
G43UF−48C−110(H) PERFORMANCE (Less Filter)
External Static Air Volume / Watts at Different Blower Speeds
External
Static
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2160 1020 880 1880 890 755 1490 705 602 1235 580 485
0.10 25 2100 990 850 1855 875 730 1480 700 585 1230 580 475
0.20 50 2035 960 805 1815 860 690 1475 695 560 1225 580 460
0.30 75 1965 925 750 1755 830 650 1475 695 545 1220 575 445
0.40 100 1885 890 725 1715 810 625 1465 690 510 1215 575 430
0.50 125 1780 840 680 1630 770 580 1420 670 490 1150 540 400
0.60 150 1690 800 660 1550 735 550 1360 640 460 1110 525 380
0.70 175 1575 745 620 1410 665 505 1210 570 405 1035 490 350
0.80 200 1375 650 550 1230 580 450 1125 530 380 970 460 325
0.90 225 1225 580 520 1120 530 415 1050 495 365 885 420 310
NOTES − All air data is measured external to unit without filter (not furnished − field provided).
Air volume based on bottom air return air. Actual air volume may vary on side return air applications.
G43UF−60C−110 PERFORMANCE (Less Filter) − Single Side Return Air − Air volumes in bold require field fabricated transi-
tion to accommodate 20 x 25 x 1 in. (508 x 635 x 25 mm) air filter in order to maintain proper air velocity.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 02625 1240 1350 2310 1090 1080 1885 890 885 1515 715 700
0.10 25 2570 1215 1330 2325 1095 1060 1910 900 865 1575 745 700
0.20 50 2410 1135 1305 2285 1080 1035 1930 910 845 1620 765 690
0.30 75 2425 1145 1265 2230 1055 990 1925 905 825 1635 770 675
0.40 100 2335 1100 1220 2175 1025 950 1910 900 810 1640 775 660
0.50 125 2270 1070 1195 2120 1000 935 1895 895 785 1640 775 640
0.60 150 2170 1025 1155 2045 965 885 1860 875 765 1630 770 630
0.70 175 2110 995 1130 1950 920 855 1795 845 730 1590 750 610
0.80 200 2035 960 1090 1885 890 820 1745 825 705 1540 725 580
0.90 225 1900 895 1055 1760 830 780 1665 785 680 1470 695 565
G43UF−60C−110 PERFORMANCE (Less Filter) − Bottom Return Air, Side Return Air with Optional RAB Return Air Base, Re-
turn Air from Both Sides or Return Air from Bottom and One Side.
External Static Air Volume / Watts at Different Blower Speeds
Pressure High Medium−High Medium−Low Low
in. w.g. Pa cfm L/s Watts cfm L/s Watts cfm L/s Watts cfm L/s Watts
0.00 0 2720 1285 1385 2410 1135 1090 2055 970 935 1620 765 710
0.10 25 2665 1255 1355 2385 1125 1075 2025 955 885 1730 815 735
0.20 50 2585 1220 1315 2350 1110 1015 2030 955 865 1680 795 690
0.30 75 2505 1180 1275 2290 1080 990 2025 955 840 1695 800 675
0.40 100 2435 1150 1250 2235 1055 940 2030 960 830 1695 800 660
0.50 125 2350 1110 1205 2170 1025 930 1975 930 790 1735 820 665
0.60 150 2255 1065 1185 2100 990 895 1915 905 765 1720 810 650
0.70 175 2160 1020 1150 2005 945 840 1865 880 730 1680 795 635
0.80 200 2020 955 1090 1905 900 825 1810 855 710 1625 765 610
0.90 225 1910 900 1050 1820 860 795 1705 805 675 1540 725 590
NOTES − All air data is measured external to unit without filter (not furnished − field provided).