THE CHIMNEY SYSTEM

Chimney Installation Notes

1.If possible, install an interior chimney as it will provide better per- formance. In areas with continuous temperatures below 18°C (0°F), the use of an exterior chimney increases the likelihood of operating problems such as low draft, high rate of creosoting, and poor start-up characteristics. Exterior chimneys are also prone to down-drafting and flow reversal. Installations which are located on lower floors in the house, such as in a basement, in combination with an outside chimney, are especially prone to flow reversal.

2.The fireplace model MONTEST may be installed only with Security Chimneys International Ltd 7” dia. chimney systems model Secure Temp™ S2100+ / Nova Temp™ HT6000 / Secure Temp GX (U.S. only) or ACBI.

3.A chimney venting a fireplace shall not vent any other appliance.

4.The minimum chimney height is 12 feet (3.7 m) excluding the fire- place.

5.All chimney installations must include at least one support in order to be able to take any lateral load. The maximum chimney length that can be supported by the fireplace is nine (9) feet (2.75 m) for Secure Temp S2100+ / Nova Temp HT6000+ / Secure Temp GX and 26 feet (8m) for ACBI chimney. In altitude, add 18” (450 mm) to the chimney for every 2,000 feet (600 m) above sea level.

6.The chimney must extend at least three (3) feet (915 mm) above its point of contact with the roof and at least two (2) feet (610 mm) higher than any wall, roof or building within ten (10) feet (3 m) of it (Figure 21).

7.If the chimney extends higher than five (5) feet (1,500 mm) above its point of contact with the roof, it must be secured using a roof brace.

8.A rain cap must be installed on top of the chimney. Failure to install a rain cap may cause corrosion problems.

9.Cut and frame square holes in all floors, ceilings, and roof that the chimney will go through to provide a 2” (50 mm) clearance between the chimney and any combustible materials. Do not fill this 2” space with insulation or any other combustible material.

10.Portions of the chimney which may extend through accessible spaces must be enclosed to avoid contact with combustible materials or damage to the chimney.

11.When offsets are used, the pipe may not penetrate a ceiling or floor unless it is running vertical (no 30° offsets).

two (2) feet Min.

ten (10) feet

 

 

 

three (3) feet Min.

 

 

 

 

 

 

 

Figure 21

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.