NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE. 3
These fi replace systems are designed for in-
stallation in accordance with the National Fire
Protection Standard for chimneys, fi replaces
and solid fuel burning appliances; NFPA 211-
latest edition and in accordance with codes
such as the BOCA Basic/National Codes, the
Standard Mechanical Code and the Uniform
Building Codes.
Note: These fi replace systems are not diffi cult
to install. However, in the interest of safety, it is
recommended that the installer be a qualifi ed or
certifi ed “tradesman” familiar with commonly
accepted fi replace installation and safety tech-
niques as well as prevailing local codes.

INTRODUCTION

General Information

These fi replaces are traditional radiant heat
replaces with standard bar grates, optional
Outside Air Kits (required for outdoor installa-
tions) and optional Operable Bi-Fold Stainless
Outdoor Glass Doors and Weather Cover.
These appliances are approved for installation
indoors or outdoors.
Indoors: These appliances are approved
for installation in residential homes and
other buildings of conventional construction
including commercial, not in manufactured
homes(see Figure 5).
Outdoors: These appliances are approved for
installion against an outside wall of a house,
or as a freestanding fi replace on the porch,
patio, or located in the yard (see Figure 6).
The Outdoor Fireplace must be enclosed to
prevent impact damage to the outside of the
fi replace. Build an outside enclosure out of
standard building materials, being careful to
maintain the minimum air clearances speci-
fi ed in these Installation Instructions. When
installing the fi replace as a freestanding unit
on your porch, patio or backyard, it must also
be enclosed to prevent impact damage to the
fi replace. However, the enclosure must now
be fi nished on all four (4) sides. The exterior
of the enclosure may be fi nished in a textured
plywood, a wood clapboard siding, brick, or
a cultured stone.
TYPICAL INSTALLATION - OUTDOORS
Chimney Section
(FTF8-48)
*Air Inlet
(Provided)
Flashing
(Locally
Fabricated)
Storm Collar
(FSC)
Metal Safety Strips
And Hearth Extension
Required When Installed
On Combustible Floor
Or In Proximity To
Combustible
Floor/Covering.
TYPICAL INSTALLATION - INDOORS
Outside
Combustion
Air Kit
(Optional)
Chimney and
Termination

Figure 1 Figure 2

Vinyl siding is not recommended for use
on the front of the fi replace due to the heat
the unit produces. This can cause the vinyl
siding to deteriorate.
Note: Illustrations shown refl ect “typical”
installations with nominal dimensions and
are for design and framing reference only.
Actual installations may vary due to individual
design preferences. However, always maintain
minimum clearances to combustible materials
and do not violate any specifi c installation
requirements.
These fi replaces have been tested and listed
by OMNI-Test Laboratories, Inc. (Report No.
116-F-35-2) to U.L. 127 (USA) and U.L.C.
S610 (Canada). These units are intended for
indoor and outdoor installations as specifi ed
in this manual.
For installations in Canada, the chimney clear-
ance to combustibles must be 2 inches and
the Cold Climate Kit must be installed.
* Outside Air Kit (provided)
must be installed in
outdoor installation.
Use Only Non-Combustible Materi-
als From Top Of Spacers Down And
Within 1/2" Min. To Side Frame.
Outside Air Kit installa-
tion is optional unless
mandated by local build-
ing codes.
Note: Framing and fi replace shown as reference
only. It can differ according to design and local
building codes.
Notes:
• Framing is shown as
reference only. It can differ
according to design and
local building codes.
• Fireplace is shown for
illustration purposes only.
It may differ from actual
model.
7' 3" Min. (using one 4' section)
Termination (FTF8-CTD/CTDT)
WARNING
Do not pack or fi ll required air spaces with insulation or other material. No material is allowed in these areas.
AVERTISSEMENT
Ne remplissez pas les espaces libres d’une matière isolante ou de tout autre type de matériel. Aucun matériel n’est permis dans ces espaces vides.
WARNING
If insulation is used, the fi replace must not be placed directly against it. Insulation or vapor barriers, if used, must fi rst be covered with gypsum board, plywood, particle board or other material to assure insulation and vapor barriers remain in place.
AVERTISSEMENT
Si un isolant est utilisé, il ne doit pas venir en contact avec le foyer. L’isolant ou le coupe vapeurs, si utilisée, doit d’abord être couvert d’un panneau de gypse, contre-plaqué, panneau de particules ou d’un autre matériel pour s’assurer que l’isolant et le coupe vapeurs demeurent en place.
Outdoor fi replace
system less than 15
feet height must be a
minimum of 10 feet
away from a building or
combustible structure.
If installed closer than
10 feet, the 10 Foot
Rule applies (see Ten
Foot Rule Summary on
Page 15).
Side Frame