10 NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Pipe Clearances
All installations using a vertical termination cap must maintain one inch
clearance between the direct-vent pipe and combustibles. For horizontal
runs of pipe, one inch of clearance to combustibles on the sides and
bottom and two inches on the top of the pipe is required. See Page 16
for allowable pipe configurations.
5-5/8”
(143mm)
10”
(254mm)
8-7/8”
(225mm)
Leg on Combustible
Carpet
1-1/2” Maximum
Clearances to Combustibles
Minimum clearances to combustible materials in inches (millimeters):
Corner Installation
Alcove dimensions
The minimum width between the alcove side walls is 51” 1295mm).
The minimum height of the alcove is 46” (1168mm) and the maximum
depth is 35” (889mm).
Floor Protection
A non-combustible hearth pad is not required. This stove may be installed
on a combustible surface as long as the combustible material (such as
carpeting) does not extend 1-1/2” (38 mm) vertically above the bottom
of the base. Also, the floor beneath the stove must be stable, level, hard
and strong enough to support the stove without a tipping hazard.
51”
(1295 mm)
Min.
35”
(889 mm)
Max.
46”
(1168 mm)
Min.
Alcove Dimensions
Figure 4
Figure 5
Figure 6
2” (51 mm)
15” (381 mm)
Min.
24-1/4”
(616 mm)
Min.
90°
10”
(254mm)
Figure 7
Parallel Installation