Vent Free Appliances
This unit has been tested and approved to ANSI/IAS/AGA Z21.11.2 for use with unvented gas appliances for INDOOR INSTALLATIONS ONLY and complies with the standard for Factory
Special instructions with regards to mantel installations must be taken into consideration when installing such appliances.
The unit has been tested for use with any unvented log sets having a maximum rating of 26,000 BTU in Indoor installations only. The minimum mantel configuration for these log sets are outlined in Figure 52.
Log sets with 40,000 BTU may be installed provided that no combustible mantel projections are placed lower than 18 inches from the fireplace opening.
These fireplaces have been marked with a maximum rating of 26,000 BTU to assure that homeowners do not exceed the allowable limits for all allowed installations of mantels. That limit may be increased to 40,000 BTU, provided that the mantel installed complies with the
IMPORTANT
Allow minimum 1"* chimney air space to combustible framing members throughout vertical or offset chimney installation.
ATTENTION
Permettez1minimal”*l’espace aérien de cheminée aux mem- bres encadrants combustibles partout dans vertical ou à l’installation de cheminée de rejeton.
*Note: In Canada, a 2” clearance to combustibles is required.
•Outdoor installations less than 15’ height require chimney clearance of 2” air space to insulation and construction materials.
WARNING
Unvented Gas Log Sets are not approved for use with fireplaces installed outdoors. The materials and components will deteriorate prematurely if installed outside. Refer to the log manufacturer’s literature for limitations and exceptions.
AVERTISSEMENT
Les ensembles de bûches à gaz sans conduit d’évacuation ne sont pas approuves pour l’usage avec des foyers installes a l’exterieur. Lesmateriauxetlescomposantes sedeteriorerontprematurementsi installees a l’exterieur. Referez- vous a la litterature du fabricant des buches pour les limites et les exceptions.
CAUTION
Plumbing connections should only be performed by a quali-
fied, licensed plumber. Main gas supply must be off when plumbing gas line to fireplace or performing service.
ATTENTION
Les raccordements de tuy- auterie devraient seulement etre effectues par un plombier qualifie et autorise. La valve d’alimentation de gaz princi- pale doit etre fermee lors de l’installation ou de l’entretien de ce foyer.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
If you’re installing a gas line, connect it before the fireplace is framed and enclosed in the finished wall. The gas knockout is determined by the indentation located at the bottom and slightly off center in the side refractories. THE
KNOCKOUT IS ALWAYS REMOVED FROM INSIDE THE FIREPLACE. DO NOT REMOVE THE KNOCKOUT UNLESS YOU ARE INSTALLING A GAS LINE. If removal is attempted from the outer wrapper, side refractory damage may occur. With a
IMPORTANT: REPACK INSULATION MATERIAL IN SQUARE HOLE AROUND GAS LINE, INTERIOR AND EXTERIOR OF FIREPLACE, TO SEAL.
Glass Doors
If glass doors are to be installed on these fireplaces, refer to specific installation instructions packed with the glass doors. Use only the doors that are listed for use with these fireplaces. Use of other
CAUTION
Certain glass doors overlap the blackmetalfacingofthefireplace. IFthefireplacehasbeenfacedwith noncombustible materials, there might not be sufficient clearance to install the glass doors of your choice.Ensureadequateclearance ismaintainedatalltimessoasnot tointerferewiththeinstallationand operation of glass doors.
19