Specifications
27
Agency
Safety UL 1778, c-UL Listed
Surge
ANSI C62.41, Category A, Level 3
(IEEE 587, Category A);
EN61000-4-5, Level 3, Criteria B
ESD EN61000-4-2, Level 3, Criteria B
Susceptibility EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient EN61000-4-4, Level 4, Criteria A
Emissions FCC Part 15, Class B FCC Part 15, Class A
Conducted Immunity EN61000-4-6
Harmonics EN61000-3-2
Flicker EN61000-3-3
Transportation ISTA Procedure 1A Certification
Table 4 Battery cabinet specifications
Model Number PS2-48VBATT PS2-72VBATT
Used w/UPS Model PS1000RT2-120
PS1440RT2-120
PS1920RT2-120
PS2200RT2-120
PS3000RT2-120
Dimensions, W x D x H, in (mm)
Unit 3.43 x 22 x 17 (87 x 557 x 430) 3.43 x 24.1 x 17 (87 x 612 x 430)
Shipping 11.8 x 27.8 x 23.5
(300 x 706 x 598)
13.1 x 34 x 23.5
(333 x 864 x 598)
Weight, lbs (kg)
Unit 66.1 (30) 101.4 (46)
Shipping 85.1 (38.6) 118.1 (53.6)
Battery Parameter
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating 2 strings of 4 x 12V x 7Ah 2 strings of 6 x 12V x 9Ah
Battery Manufacturers CSB, B&B Battery and EnerSys
Backup Time See Table5 - Battery run times
Environmental
Operating Temperature +32°F to + 104°F (0°C to + 40°C)
Storage Temperature +5°F to + 104°F (-15°C to + 40°C)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class B
Transportation ISTA Procedure 1A Certification
Table 3 UPS specifications (continued)
Model Number PS1000RT2-120 PS1440RT2-120 PS1920 RT2-120 PS2200RT2-120 PS3000RT2-120