2.2.2Bi-Directional Converter 2.2.2.1 General
The
1.In Normal mode of operation, the
2.In Battery mode of operation, the
3.In the recharge mode of operation, the
2.2.2.2Battery Recharge
The UPS contains a battery recharge rate designed to prolong battery life. The battery is constant voltage charged to recharge and maintain the battery in a fully charged state. Recharge time is 6 hours maximum to 90% rated capacity after discharge into full resistive load.
2.2.2.3Bi-Directional Converter DC Protection
The following DC shutdown levels protect the UPS:
DC Overvoltage Shutdown
DC Undervoltage Shutdown (End of Discharge)
DC Undervoltage Warning (Low Battery Reserve)
2.2.2.4Output Protection
For output faults including short circuits and overloads, the UPS is protected by the input circuit protector during Normal mode and by electronic current limiting during Battery mode.
2.2.2.5Overload
The UPS is capable of supplying power for overloads exceeding 100% and up to 110% of full load rating, continuously. A visual indicator and audible alarm indicate overload operation. For greater current demands, the UPS employs circuit protector and electronic
2.2.2.6Output Frequency
An oscillator controls the output frequency of the UPS. The oscillator maintains the output frequency to + 0.5 Hz of nominal when not synchronized to the utility/mains source.
2.2.2.7Battery Over-Discharge Protection
To prevent battery damage due to excessive discharge levels, the UPS control logic automatically monitors the battery voltage and load level and switches off the output at the predetermined battery shutdown voltage set point.
PowerSure PSA | 6 | Guide Specification |
350 – 1000VA |
|