Liebert OpenComms™ 485
Quick Start Guide
INSTALL
•Locate the Intellislot option for your Liebert equipment.
•You might need to remove a plastic Intellislot cover.
•Insert the OpenComms 485 Card into the Intellislot bay.
•Secure the card with the supplied screws.
•Connect
IGM: The card ships with IGM service enabled. (No configuration is required for IGM communications.)
Modbus: To assign a server ID address, use the Service Terminal to configure the card. Proceed to Steps 2 & 3.
CONNECT THE CABLE
•Locate the blue serial configuration cable (null modem) that shipped with the card.
•Connect the configuration cable to the
CONFIGURE THE CARD
•Use terminal emulation software, such as HyperTerminal™, to open a direct connection to the card.
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None
•Press ENTER for the Main Menu, above right.
•Select option 1 and press enter to access the communications settings, shown at right.
•Enter 1 and press enter to enable the Modbus application.
•At the next screen, enter 3 to access the screen to set the server ID for the
•Press Esc to return to the Main Menu.
•Enter X and press Enter to exit HyperTerminal, save your changes and reboot the card.