Figure 2 Capacity correction factor

Table 4

Drycooler performance data (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBH/°F Initial Temperature Difference

 

 

Model

GPM

No. of

1.5 GPM/CIR

 

2.0 GPM/CIR

2.5 GPM/CIR

3.0 GPM/CIR

Number

Range

Circuits

MBH/ITD

PD ft. water

MBH/ITD

PD ft. water

MBH/ITD

PD ft. water

MBH/ITD

PD ft. water

Quiet-Line Models

 

 

 

 

 

 

 

 

 

 

040

6-12

4

1.4

7.4

 

1.5

11.4

1.6

17.0

1.7

23.5

 

12-24

8*

1.6

3.9

 

1.7

5.9

1.8

8.9

1.8

12.3

057

18-36

12*

2.1

3.6

 

2.2

6.1

2.3

8.6

2.3

11.9

 

24-48

16

2.2

3.0

 

2.3

4.6

2.3

6.2

2.4

8.6

060

12-24

8

2.2

7.1

 

2.3

11.3

2.4

16.6

2.5

23.0

 

24-48

16*

2.4

3.8

 

2.5

5.9

2.5

8.1

2.5

11.3

080

12-24

8

2.7

6.2

 

3.0

9.8

3.2

14.5

3.3

20.1

 

24-48

16*

3.2

3.3

 

3.4

5.1

3.6

7.0

3.7

9.7

111

24-48

16*

4.4

4.7

 

4.3

7.4

4.4

10.4

4.5

14.3

 

36-72

24

4.2

3.2

 

4.4

4.8

4.6

7.2

4.6

10.0

121

24-48

16*

4.4

6.1

 

4.7

9.7

4.8

13.7

4.9

18.9

 

48-96

32

4.8

2.9

 

4.9

4.9

5.0

7.0

5.1

9.6

158

24-48

16

5.6

6.4

 

6.0

10.3

6.3

14.7

6.6

20.3

 

36-72

24*

6.0

4.3

 

6.4

6.7

6.6

10.0

6.8

13.8

173

24-48

16

6.1

8.4

 

6.6

13.5

6.9

19.5

7.1

26.9

 

48-96

32*

6.9

4.1

 

7.2

6.8

7.4

9.7

7.5

13.5

178

24-48

16

6.5

12.3

 

6.9

20.0

7.1

29.1

7.3

40.1

 

48-96

32*

7.1

6.0

 

7.3

10.0

7.4

14.5

7.5

20.0

 

72-144

48

7.3

4.1

 

7.4

6.6

7.5

9.9

7.6

13.3

205

24-48

16

6.9

8.2

 

7.7

13.2

8.2

18.9

8.6

26.2

 

36-72

24*

7.8

5.5

 

8.4

8.7

8.8

12.9

9.0

17.6

248

24-48

16

7.6

10.7

 

8.5

17.4

9.1

25.2

9.4

34.8

 

48-96

32*

9.1

5.2

 

9.6

8.7

9.9

12.5

10.1

17.3

347

48-96

32

12.2

8.0

 

13.2

13.3

13.9

19.4

14.3

26.8

 

96-192

64*

13.8

4.1

 

14.4

6.7

14.8

9.7

15.0

13.4

356

48-96

32

12.9

11.9

 

13.8

19.8

14.3

29.0

14.5

40.0

 

96-192

64*

14.2

6.0

 

14.7

9.9

14.9

14.4

15.0

20.0

 

144-288

96

14.6

4.0

 

14.9

6.6

15.0

9.6

15.2

13.3

453

48-96

32

15.2

10.3

 

17.0

17.2

18.1

25.1

18.9

34.7

 

96-192

64*

18.2

5.2

 

19.2

8.7

19.9

12.5

20.3

17.3

498

48-96

32

16.1

15.4

 

17.8

25.6

18.8

37.6

19.2

51.8

 

96-192

64

18.8

7.7

 

19.5

12.8

19.9

18.6

20.1

25.7

 

144-288

96*

19.5

5.1

 

20.0

8.5

20.2

12.4

20.4

17.2

* Standard Circuiting

Based on 40% Ethylene Glycol Solution at 115°F average solution temperature expressed in MBH. Specifications subject to change without notice.

Figure 2 Capacity correction factor

Figure 3 Pressure drop correction factor

Glycol % and average temperature °F

Glycol % and fluid temperature °F

Correction Factor

Correction Factor

Average Fluid Temperature

Average Fluid Temperature

5

Page 9
Image 9