Liebert AC4 manual Description, Features and Benefits, Product Specification/Installation Sheet

Models: AC4

1 4
Download 4 pages 49.53 Kb
Page 1
Image 1
Product Specification/Installation Sheet

AC4

Product Specification/Installation Sheet

Description

The Liebert AC4 is ideal for coordinated control of systems with redundant equipment, such as multiple environmental units or pumps. When the AC4 controller detects an alarm in an operating device, the AC4 enables a standby device and controls the device in alarm as configured, either leaving that device operating or disabling it.

The AC4 controller can also balance usage of devices by rotating

units through Operating and Standby modes according to a user-defined schedule. This helps keep redundant equipment operating efficiently and only when needed. The AC4 can perform routine testing of standby devices and alert personnel if a standby device fails an operating test and requires attention.

Another capability of the AC4 is monitoring the status of connected devices and keeping personnel apprised through local alarming.

The AC4 controller can interface with anything that closes an electrical contact. To improve process efficiency and troubleshooting, the controller tracks data in two types of logs: alarm and event. The AC4 has a local LCD interface and an RS232 interface.

When an alarm condition arises, the AC4 displays alarm information, sounds an audible alarm, changes the state of the common alarm relay and turns connected devices on or off according to user configuration.

For other applications, contact your local Liebert representative or call 1-800-222-5877.

Features and Benefits

Custom configuration for specific applications

Alarm and Event logs with time and date stamp

Backup and download configuration files

User interface for configuration and monitoring via local LCD or RS232 port

On-board audible alarm

Configuration data and operating program permanently stored in nonvolatile Electrically Erasable Programmable Read Only Memory (EEPROM) for protection against power loss

Real-time clock

Status LEDs for verification and diagnostics

AC4 Components and Key Features

Power On/Off switch

Audible horn

Audible horn

Common Alarm connectors

jumper

 

Digital output status LEDs

24VAC power connector

 

Manual Override Switch

LCD contrast

(outputs)

adjustment

Digital output connectors

 

LCD connector

Status LEDs

 

DIP switch 1

Digital output loss-of-power

 

jumper

Digital input connectors

Serial interface connector

Digital input status LEDs

(RS232/EIA574)

1

Page 1
Image 1
Liebert AC4 manual Description, Features and Benefits, Product Specification/Installation Sheet