Liebert Datawave® Magnetic Synthesizer

Specifications

60Hz

 

 

 

Three

Input

 

 

 

Heat Output

 

 

 

Phase

Circuit

Panel

Dimensions

 

(BTU/Hr)

 

Output

 

Input

Breaker

Board

(in)

Weight

@ Full Load

 

kVA

kW

Voltage1

(Amps)

Poles2

(Wx D xH)

(lbs)

PF=1

 

15

15

208

60

42

36x34x64

1,200

6,350

 

 

 

 

480

30

 

 

 

 

 

 

 

 

600

25

 

 

 

 

 

20

20

208

80

42

36x34x64

1,500

8,450

 

 

 

 

480

40

 

 

 

 

 

 

 

 

600

30

 

 

 

 

 

30

30

208

125

42

36x34x64

1,600

10,125

 

 

 

 

480

50

 

 

 

 

 

 

 

 

600

50

 

 

 

 

 

50

50

208

200

84

44x32x68

2,400

12,850

 

 

 

 

480

90

 

 

 

 

 

 

 

 

600

70

 

 

 

 

 

75

75

208

300

84

44x32x68

2,750

19,270

 

 

 

 

480

125

 

 

 

 

 

 

 

 

600

110

 

 

 

 

 

100

100

208

400

120

66x36x76

3,900

25,700

 

 

 

 

480

175

 

 

 

 

 

 

 

 

600

150

 

 

 

 

 

125

125

208

500

120

66x36x76

4,300

32,100

 

 

 

 

480

225

 

 

 

 

 

 

 

 

600

175

 

 

 

 

 

150

150

208

600

120

1043x36x76

5,800

38,500

 

 

 

 

480

250

 

 

 

 

 

 

 

 

600

225

 

 

 

 

 

200

200

208

800

120

1043x36x76

6,500

51,400

 

 

 

 

480

350

 

 

 

 

 

 

 

 

600

300

 

 

 

 

 

50Hz

 

 

 

Three

Input

 

 

 

Heat Output

 

 

 

Phase

Circuit

Panel

Dimensions

 

(kW/Hr)

 

Output

 

Input

Breaker

Board

(cm)

Weight

@ Full Load

 

kVA

kW

Voltage4

(Amps)

Poles2

(Wx D xH)

(kg)

PF=1

 

15

15

380

40

42

92x87x163

590

1.85

 

 

 

 

400

40

 

 

 

 

 

 

 

 

415

30

 

 

 

 

 

20

20

380

50

42

92x87x163

730

2.47

 

 

 

 

400

50

 

 

 

 

 

 

 

 

415

40

 

 

 

 

 

30

30

380

70

42

92x87x163

775

2.97

 

 

 

 

400

70

 

 

 

 

 

 

 

 

415

60

 

 

 

 

 

50

50

380

110

84

112x81x173

1,200

3.76

 

 

 

 

400

110

 

 

 

 

 

 

 

 

415

100

 

 

 

 

 

75

75

380

175

84

112x81x173

1,375

5.65

 

 

 

 

400

175

 

 

 

 

 

 

 

 

415

150

 

 

 

 

 

100

100

380

225

120

168x92x193

2,000

7.53

 

 

 

 

400

225

 

 

 

 

 

 

 

 

415

200

 

 

 

 

 

125

125

380

300

120

168x92x193

2,230

9.41

 

 

 

 

400

250

 

 

 

 

 

 

 

 

415

250

 

 

 

 

 

150

150

380

350

120

2643x92x193

2,950

11.29

 

 

 

 

400

350

 

 

 

 

 

 

 

 

415

300

 

 

 

 

 

200

200

380

450

120

2643x92x193

3,340

15.05

 

 

 

 

400

450

 

 

 

 

 

 

 

 

415

400

 

 

 

 

 

General Specifications

Voltage Regulation: For input voltages of ±40%, output voltage is within +5% for any load condition up to full load.

Overload Capacity: Supports 200% load until circuit breaker trips, 5 to 20 minutes typical.

Output Voltage Distortion: Less than 4% total, not additive to input distortion.

Noise Suppression: 120dB common mode and 120dB normal mode.

Efficiency: 89% for 15-20 kVA, 91% for 30 kVA, and 93% for 50-200 kVA at full load.

Input Power Factor: >0.96 half to full load, regardless of load power factor.

Unbalanced Loads: Output voltage is within +5%, -2% with 100% load current unbalance.

Single Phase Protection: For loss of one input phase, output voltages remain within 6% and –4% up to 60%load.

Audible Noise: 55-63 dBa at 5 feet.

Monitored Parameters: Input and Output Voltages; Output, Neutral and Ground Currents; Output Voltage THD; Output Current THD; K-Factor, Crest Factor; Output Power kVA, kW- Hours; Power Factor; Percent Load; Frequency.

Alarm Conditions: Output Over- and Under- voltages; Output Voltage THD; Output Overload; Neutral and Ground Overcurrents; Transformer Overtemperature; Frequency Deviation; Phase Sequence Error; Phase Loss; Five Customer Specified Alarm Conditions.

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

24 x 7 Tech Support

800 222 5877 Phone

614 841 6755 (outside U.S.)

While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 2006 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks of their respective owners.

®Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.

SL-20199 (R07/06) Printed in USA

Emerson Network Power.

The global leader in enabling Business-Critical Continuity.

AC Power Systems

Connectivity

DC Power Systems

Embedded Computing

Embedded Power

Integrated Cabinet Solutions Outside Plant

1Other input voltages available. Standard output voltages are 208/120, 480/277, and 600/346 volts. For voltages not show, consult factory.

2Panelboards furnished on "SC" models. Main output breakers furnished on "CA" models.

3For ease in shipping and handling, unit shipped in two modules of 52 inches (132 cm) each.

4Other input voltages available. Standard output voltages are 208/120, 380/220, 400/230 and 415/240 volts. For voltages not shown, consult factory.

Power Switching & Control Precision Cooling

Services

Site Monitoring

Surge Protection

Emerson Network Power.com

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2006 Emerson Electric Co.

Page 4
Image 4
Liebert Datawave manual Liebert Corporation, Liebert.com 24 x 7 Tech Support, Emerson Network Power, AC Power Systems