Liebert DCP

Three phase electric service not provided by Liebert

Factory installed unit disconnect switch

Field supplied disconnect switch may not be required, check local codes.

 

 

 

 

 

 

 

ELECTRIC CONDUIT KNOCKOUTS

Three phase electric service

 

 

 

 

 

 

On top of electric box. Knockout size

 

 

 

 

 

 

2 in (51 mm)

 

 

 

not provided by Liebert

 

 

 

 

 

 

 

 

 

 

 

 

 

THREE PHASE CONNECTION

Electric service connection terminals

EARTH GROUND LUG

Connection terminal for

field supplied earth

grounding wire.

Factory installed disconnect switch

Factory wired to components

on electric panel

60HZ COMPONETS SHOWN

Monitoring panel

CANBUS ISOLATOR

ALARM AND WARNING OUTPUT RELAYS Field supplied 24V Class 2 wire for special alarms.

(Not to exceed 1.0A @ 24v each.)

REMOTE UNIT SHUTDOWN

Replace existing jumper between terminals 37 & 38 with normally closed switch having a minimum 50VA rating. Use field supplied 24V Class 2 wire.

SITE MONITORING CONNECTION Terminals 77 (-) and 78 (+) are for connection of a 2 wire, twisted pair, communication cable (available from Liebert or others) for optional Sitescan. (see user's manual).

INTELLISLOTS®

Two Liebert Intellislots® for optional OCWEB-LBDS or OC485-LBDS card.

NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

Page 4/5

REV DATE 11/11

DPN002400

REV 0