Liebert Interceptor Hybrid

TVSS Technical Specification

Operating Frequency Range

47 - 63 Hz

Fault Current Rating (AIC)

200 kAIC

Capacity

(Continuous) Parallel

Modes of Protection

L - N, L - L, L - G, N - G

Response Time

MOVs= <0.5 nanoseconds / SADs= <250 picoseconds

Operating Temperature

-40ϒC TO 60ϒC

Operating Humidity

0% TO 95% Non-condensing

Certifications

UL 1449, UL 1283, CSA, ISO 9001

Warranty

5 Years Labor / 10 Years Parts

Example Part Number: H2120Y444R-03= 500Joules,120/208V 3-Phase Wye, 750 kA per phase, Rotary Disconnect, LED’s, Alarm & Dual Counters

H __ __ __ __ __ __ __ __ __ - __ __

Life Cycle Surge Testing

10kA, 20kV, IEEE Cat. C3

Unit

Per Mode

Per Phase

250kA

15,000

30,000

320kA

30,000

60,000

400kA

45,000

90,000

750kA

60,000

120,000

 

SAD

 

 

Option Codes

 

Surge

 

01

 

Energy

 

LED

1

250J

 

04

LED, Alarm

2

500J

 

05

LED, Surge Counter

 

 

 

06

LED, Alarm,

 

Voltage

03

Surge Counter

 

LED, Alarm, Dual

 

120

120V

 

 

Surge Counters

 

208

208V

 

 

 

 

 

230

 

230V

 

 

 

 

 

 

 

240

 

240V

 

 

Connection Type

 

 

277

 

277V

 

 

“blank”

 

Compression Lugs

 

 

480

 

480V

 

 

R

 

Rotary Disconnect

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phase Configuration

NSingle Phase L-N L Single Phase L-L S Split Phase

Y 3 Phase Wye D 3 Phase Delta H 3 Phase Hi-Leg

Surge Current Rating

111250kA Per Phase

222320kA Per Phase

333400kA Per Phase

444750kA Per Phase

Job Name____________________________

Model # _____________________________

Date ________________________________

Qty _________________________________

Quote # _____________________________

UL 1449 second edition

Voltage Modes

Clamping

 

L-N

330

120/208

L-G

400

N-G

400

 

 

L-L

700

 

L-N

700

277/480

L-G

800

N-G

800

 

 

L-L

1500

240

L-G

700

L-L

700

 

480L-G 1500

L-L 1500

Case Size

..S111

A

= 16”

..Y111

B

= 20”

..D110

C = 10”

..S222

A

= 20”

..Y222

B

= 24”

..D220

C = 10”

..S333

A

= 24”

..Y333

B

= 24”

..D330

C = 10”

..S444

A

= 24”

..Y444

B

= 30”

..D440

C = 10”

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229

 

Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169

 

EMAIL: info@control-concepts.com • Web Site: www.Liebert.com

82244 Rev 0

Page 1
Image 1
Liebert H2120Y444R-03 warranty Liebert Interceptor Hybrid Tvss Technical Specification, Life Cycle Surge Testing