60 HZ 50 HZ
CHILLED WATER
3 Tons 3 Tons
Evaporator MMD40C MMD39C
Capacity Data BTUH (kW) High Fan Speed
80 F (26.7 C) DB Total 49,200 (14.4) 49,200 (14.4)
50% RH Sensible 33,100 (9.7) 33,100 (9.7)
75 F (23.9 C) DB Total 33,900 (9.9) 33,900 (9.9)
50% RH Sensible 27,800 (8.1) 27,800 (8.1)
72 F (22.2 C) DB Total 27,100 (7.9) 27,100 (7.9)
50% RH Sensible 24,900 (7.3) 24,900 (7.3)
Capacity Data BTUH (kW) Low Fan Speed
80 F (26.7 C) DB Total 40,700 (11.9) 40,700 (11.9)
50% RH Sensible 26,900 (7.9) 26,900 (7.9)
75 F (23.9 C) DB Total 27,700 (8.1) 27,700 (8.1)
50% RH Sensible 22,300 (6.5) 22,300 (6.5)
72 F (22.2 C) DB Total 21,700 (6.4) 21,700 (6.4)
50% RH Sensible 19,800 (5.8) 19,800 (5.8)
60 HZ 50 HZ
AIR COOLED SYSTEM
with Outdoor Condensing Unit with Centrifugal Condensing Unit with Outdoor Condensing Unit with Centrifugal Condensing Unit
2 Tons 3 Tons 2 Tons 3 Tons 2 Tons 3 Tons 2 Tons 3 Tons
Evaporator MMD24E MMD36E MMD24E MMD36E MMD23E MMD35E MMD23E MMD35E
Condensing Unit PFH027A PFH037A MCD24A MCD36A PFH026A PFH036A MCD23A MCD35A
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB Total 25,600 (7.5) 36,900 (10.8) 24,200 (7.1) 34,100 (10.0) 23,800 (7.0) 34,500 (10.1) 22,700 (6.7) 31,800 (9.3)
50% RH Sensible 20,900 (6.1) 26,600 (7.8) 20,300 (5.9) 28,300 (8.3) 20,200 (5.9) 28,400 (8.3) 19,800 (5.8) 27,400 (8.0)
75 F (23.9 C) DB Total 23,800 (7.0) 34,200 (10.0) 22,400 (6.6) 31,700 (9.3) 22,100 (6.5) 32,100 (9.4) 21,000 (6.2) 29,600 (8.7)
50% RH Sensible 20,100 (5.9) 25,700 (7.5) 19,500 (5.7) 27,200 (8.0) 19,400 (5.7) 27,400 (8.0) 19,000 (5.6) 26,400 (7.7)
72 F (22.2 C) DB Total 22,900 (6.7) 32,900 (9.6) 21,400 (6.3) 30,400 (8.9) 21,200 (6.2) 30,800 (9.0) 20,100 (5.9) 28,300 (8.3)
50% RH Sensible 19,700 (5.8) 25,200 (7.4) 19,100 (5.6) 26,500 (7.8) 19,000 (5.6) 26,700 (7.8) 18,500 (5.4) 25,700 (7.5)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB Total 25,500 (7.5) 36,900 (10.8) 24,000 (7.0) 33,600 (9.8) 23,700 (6.9) 34,000 (10.0) 22,600 (6.6) 31,500 (9.2)
50% RH Sensible 19,800 (5.8) 26,600 (7.8) 19,300 (5.7) 25,300 (7.4) 19,100 (5.6) 25,400 (7.4) 18,700 (5.5) 24,400 (7.1)
75 F (23.9 C) DB Total 23,800 (7.0) 34,200 (10.0) 22,300 (6.5) 31,300 (9.2) 22,000 (6.4) 31,700 (9.3) 20,900 (6.1) 29,300 (8.6)
50% RH Sensible 19,200 (5.6) 25,700 (7.5) 18,500 (5.4) 24,300 (7.1) 18,400 (5.4) 24,600 (7.2) 18,000 (5.3) 23,600 (6.9)
72 F (22.2 C) DB Total 22,700 (6.7) 32,900 (9.6) 21,300 (6.2) 29,900 (8.8) 21,100 (6.2) 30,400 (8.9) 20,000 (5.9) 28,000 (8.2)
50% RH Sensible 18,700 (5.5) 25,200 (7.4) 18,100 (5.3) 23,900 (7.0) 18,000 (5.3) 24,100 (7.1) 17,500 (5.1) 23,100 (6.8)
60 HZ 50 HZ
WATER COOLED GLYCOL COOLED WATER COOLED GLYCOL COOLED
2 Tons 3 Tons 2 Tons 3 Tons 2 Tons 3 Tons 2 Tons 3 Tons
Evaporator MMD24E MMD36E MMD24E MMD36E MMD23E MMD35E MMD23E MMD35E
Condensing Unit MCD26W MCD38W MCD26W MCD38W MCD25W MCD37W MCD25W MCD37W
Net Capacity Data*BTUH (kW) High Fan Speed
80 F (26.7 C) DB Total 26,600 (7.8) 38,400 (11.3) 23,000 (6.7) 35,200 (10.3) 24,900 (7.3) 35,700 (10.5) 21,300 (6.2) 32,600 (9.6)
50% RH Sensible 21,300 (6.2) 29,900 (8.8) 19,900 (5.8) 28,700 (8.4) 20,600 (6.0) 28,900 (8.5) 19,300 (5.7) 27,700 (8.1)
75 F (23.9 C) DB Total 24,600 (7.2) 35,600 (10.4) 21,400 (6.3) 32,700 (9.6) 22,800 (6.7) 33,000 (9.7) 19,800 (5.8) 30,400 (8.9)
50% RH Sensible 20,400 (6.0) 28,800 (8.4) 19,100 (5.6) 27,600 (8.1) 19,700 (5.8) 27,700 (8.1) 18,500 (5.4) 26,700 (7.8)
72 F (22.2 C) DB Total 23,400 (6.9) 33,900 (9.9) 20,500 (6.0) 31,300 (9.2) 21,800 (6.4) 31,500 (9.2) 18,700 (5.5) 29,100 (8.5)
50% RH Sensible 19,900 (5.8) 28,100 (8.2) 18,700 (5.5) 27,000 (7.9) 19,200 (5.6) 27,100 (7.9) 18,700 (5.5) 26,000 (7.6)
Net Capacity Data*BTUH (kW) Low Fan Speed
80 F (26.7 C) DB Total 26,200 (7.7) 37,400 (11.0) 22,700 (6.7) 34,200 (10.0) 24,500 (7.2) 34,600 (10.1) 21,100 (6.2) 31,800 (9.3)
50% RH Sensible 20,100 (5.9) 26,700 (7.8) 18,800 (5.5) 25,500 (7.5) 19,500 (5.7) 25,700 (7.5) 18,200 (5.3) 24,600 (7.2)
75 F (23.9 C) DB Total 24,200 (7.1) 34,400 (10.1) 21,100 (6.2) 31,800 (9.3) 22,600 (6.6) 32,000 (9.4) 19,600 (5.7) 29,600 (8.7)
50% RH Sensible 19,400 (5.7) 25,800 (7.6) 18,100 (5.3) 24,700 (7.2) 18,700 (5.5) 24,800 (7.3) 17,500 (5.1) 23,700 (6.9)
72 F (22.2 C) DB Total 23,000 (6.7) 32,900 (9.6) 20,300 (5.9) 30,500 (8.9) 21,500 (6.3) 30,600 (9.0) 18,800 (5.5) 28,300 (8.3)
50% RH Sensible 18,900 (5.5) 25,200 (7.4) 17,700 (5.2) 24,100 (7.1) 18,200 (5.3) 24,200 (7.1) 17,000 (5.0) 23,200 (6.8)
*The net capacity data has fan motor heat factored in for all ratings and the entering air condition of 72˚F (22.2˚C), 50% RH is the standard rating condition of ASHRAE 127-2001
9
Specifications
2 And 3 Ton Split Systems