Indoor/Outdoor Process Chiller
Designed for GE Signa or 1.5T Excite
•Dedicated,
•
•Clean,
•Local service and parts for quick and knowledgeable maintenance and service.
•Optional
•Optional remote monitoring systems keep you informed of chiller operation.
•Standard product ETL/CSA certified.
•ISO 9000 certified company.
Signa Horizon & CV Specifications |
|
|
| ||
Fluid Specified |
| Water/Glycol |
|
|
|
|
|
|
|
|
|
Max Heat Dissipation - BTUH (kW) | 28,320 (8.3) |
|
|
| |
|
|
|
|
|
|
Fluid Temperature Range, °F (°C) |
|
|
| ||
|
|
|
|
|
|
Temperature Gradient |
| N/A |
|
|
|
|
|
|
|
|
|
Fluid Flow Rate - GPM (l/m) | 2.1 (8.0) |
|
|
| |
|
|
|
|
|
|
Fluid Pressure Drop - PSI (kPa) | 36.0 (248) |
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
Liebert Process Chiller Specifications |
| ||||
Model Number |
| PS036A |
| PS036A | PS036A |
|
|
|
|
|
|
Fluid Circulated |
| Water |
| Ethylene Glycol | Propylene Glycol |
|
|
|
|
|
|
Net Cooling Capacity - BTUH (kW) |
| 29,500 (8.6) |
| 29,600 (8.7) | 28,800 (8.4) |
|
|
|
|
|
|
Leaving Fluid Temperature ° F (° C) |
| 50 (10) |
| 53 (11.7) | 56 (13.3) |
|
|
|
|
|
|
Fluid Flow Rate - GPM (l/m) |
| 5.3 (20.1) |
| 5.3 (20.1) | 5.3 (20.1) |
|
|
|
|
|
|
Signa Horizon & CV Pressure Drop - PSI (kPa) |
| 36.0 (248) |
| 48 (331) | 55.1 (380) |
|
|
|
|
|
|
Chiller Pressure Drop - PSI (kPa) |
| 5.1 (35.2) |
| 6.8 (46.9) | 7.8 (53.8) |
|
|
|
|
|
|
Pump Total Head - PSI (kPa) |
| 64.9 (448) |
| 64.9 (448) | 64.9 (448) |
|
|
|
|
|
|
Pump HP (kW) |
| 3 (2.2) |
| 3 (2.2) | 3 (2.2) |
|
|
|
|
|
|
Indoor/Outdoor Process Chiller Designed for GE Signa or 1.5T Excite | 1 |