3000 VA GX SPECIFICATIONS
Model Rating (VA/Watts) 3000 VA / 2100 W at 240 VAC, 2600 VA / 1820 W at 208
VAC
INPUT
Voltage 240 VAC or 208 VAC, 3-Wire plus Ground
Voltage Range +10%, -20% (transfer to battery at 21%)
Frequency 47 to 63 Hz
Current 15 Amps (12 Amps RMS per phase)
Power Factor Minimum .94 at Full Load
Voltage Transients Meets Requirements of IEEE 587 Category A & B
Power Cord 6’ / 1.88 m w/NEMA L14-20 Plug (20 A)
OUTPUT
Voltage and Current 120 VAC at 25 A, 208 VAC at 12.5, 240 VAC at 12.5 A
Voltage Regulation ±3%
Frequency Locked to Utility Selected nominal 50 or 60 Hz ± 1Hz
Output Distortion Maximum 5 % THD with non-linear load
Waveform Sinewave
Overload 150% Full Load Amps for 10 Cycles Max, 120 % Full Load Amps
for 1 Sec
Load Power Factor Range 0.6 Lagging pf to Unity (Rated at 0.7 pf)
Transient Response Time 100% Full Load Amps for 10 Cycles Max, 120 % Full Load Amps
for 1 Sec
Bypass Transfer 4 6 Milliseconds
Efficiency (AC to AC) 85% at 100% Load
Receptacles 4 NEMA 5-15R (2 Duplex), 1 NEMA L6-30, 1 NEMA L12-
20
BATTERY
Backup w/1 Ext. Cabinet 10 Minutes
Backup w/2 Ext. Cabinets 25 Minutes
Backup w/3 Ext. Cabinets 50 Minutes
Battery Quantity 6 per Cabinet (1 to 3 cabinets may be connected)
Nominal Voltage 72 VDC
Battery Rating 12 V / 15 AH
Transfer Time Uninterrupted
Battery Recharge Time 4 Hours to 90% (10 Minute Discharge Rate, 1 Cabinet)
Battery Type Sealed, Maintenance-Free
ENVIRONMENTAL
Operating Temperature 10° to 35° C
Storing Temperature -20° to 40° C with Battery, -35° to 50° without Battery
Relative Humidity 0 to 95% Non-Condensing
Operating Attitude Full Rating, Up to 3,000 M 10% Derating per 1,000 M above
3,000 M
Electromagnetic Noise Meets FCC Part 15, Subpart J, Class A
Audible Noise 52 dBA at 1 Meter
Agency Approvals UL 1778, CSA No. 107
PHYSICAL
Dimensions HxW*xD 7” x 17” x 21” / 177 mm x 432 mm x 534 mm
UPS Weight 49 lbs. / 22.2 kg
External Cabinet Weight 111 lbs. / 50.3 kg
Rear & Front Clearance 4” / 102 mm