13
SPECIFICATIONS
Typical Transfer Time
(to or from maintenance bypass) < 6 milliseconds
Input Voltage Nominal 208VAC or 240VAC
Total Current 30A max.
Operating Ambient Temperature 0° to +40° C
Storage Ambient Temperature -20° to +60° C
Dimensions, W x D x H, in (mm) 8.2 x 21.0 x 6.2 (209 x 534 x 158)
Chassis Weight (no receptacles) 10 lbs.
Distribution Module Weights (each) 2 lbs.
Connections to UPS Hardwire Terminal Blocks
Humidity 0 to 95%, non-condensing
Agency/Standards UL 1778, c-UL