Specifications

Liebert XDR-W RackCooler™

Nominal Capacity

8 kW / 2.2 Ton

Nominal Airflow

1000 CFM (1700 m3/h)

Input Voltage

120 V, 1 ph, 60 Hz

 

230 V, 1 ph, 60 Hz

Full load amps

1.5A @ 120V

Height

55.5” (1410 mm)

Width

15” (381 mm)

Depth

6” (152 mm)

Weight

70 lbs (32 kg)

Liebert XDR-W modules are connected via quick-connect couplings to a Liebert XDP-W that controls coolant flow temperature and acts as an interface with your building’s chilled water system through a heat exchanger.

Hydraulic Schematic

Liebert Corporation

1050 Dearborn Drive

P.O. Box 29186

Columbus, Ohio 43229

800 877 9222 Phone (U.S. &

Canada Only)

614 888 0246 Phone (Outside U.S.)

614 841 6022 FAX

Via Leonardo Da Vinci 8

Zona Industriale Tognana

35028 Piove Di Sacco (PD)

Italy

39 049 9719 111 Phone

39 049 5841 257 FAX

Emerson Network Power Asia Pacific

7/F., Dah Sing Financial Centre

108 Gloucester Rd, Wanchai

Hong Kong

852 25722201 Phone

852 28029250 FAX

liebert.com

24 x 7 Tech Support

800 222 5877 Phone

614 841 6755 (outside U.S.)

While every precaution has been taken to ensure accuracy and completeness in this literature, Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.

© 2007 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice.

All names referred to are trademarks or registered trademarks of their respective owners.

®Liebert and the Liebert logo are registered trademarks of the Liebert Corporation.

SL-16750 (R10/07) Printed in USA

Emerson Network Power.

The global leader in enabling

Business-Critical Continuity.

AC Power

Connectivity

DC Power Embedded Computing

Embedded Power

Monitoring

Outside Plant

BUILDING

 

 

DUAL

CHILLED

 

 

PUMPS

WATER

 

 

 

LOOP

 

 

 

 

 

 

 

 

 

 

 

HEAT

EXCHANGER

2-WAY VALVE CONTROLS SECONDARY FLUID ABOVE ROOM DEWPOINT

Low pressure water circuit with a fluid temperature always above the actual dewpoint, to prevent condensation.

Up to 12 Liebert XDR-W units can be piped to each coolant distribution unit, XDP-W.

Power Switching & Controls

Precision Cooling

Racks & Integrated Cabinets Services

Surge Protection

Emerson Network Power.com

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2007 Emerson Electric Co.

Page 2
Image 2
Liebert XDR-W manual Specifications