Liebert S, Y, 100 - 2, LPM, H dimensions Job Name Model# Date Qty Quote#, 160 kA/Phase, 100 kA/Phase

Models: Y S 160 277 LPM H 100 - 2

1 1
Download 1 pages 22.72 Kb
Page 1
Image 1
160 kA/Phase

Liebert AC Power Medium Exposure Transient Voltage Surge Suppressor, a surge protective device designed with sine wave tracking to protect electronic equipment and microprocessor-based systems from transients on distribution panels or any medium exposure locations.

160 kA

100 kA

AC Power Medium Exposure TVSS Technical Specification

Connection Type

 

Parallel

Operating Voltage Range

 

+/-15%

Fault Current Rating (AIC)

(160 kA units)

65 kAIC

Dimensions

8”x6”x4”

..............................................

(100 kA units)

6”x4”x3”

Operating Frequency Range

47 – 63 Hz

Capacity

 

Continuous

50 ￿ EMI/RFI Attenuation

 

40 dB

Response Time

 

<0.5 ns

Operating Humidity

 

0% to 95%

Operating Temperature

 

-40º c to +50ºc

Dry Contact Rating

 

125vac, 8.0A, 1.0pf

Status Indication

 

LEDs, Dry Contacts

Certifications

 

UL 1449, CUL, ISO 9001

Warranty

 

5 Years Parts

 

UL 1449 (second edition) Classification

 

120 volt systems

400 volts all modes

 

208 and 277 volt systems

800 volts all modes

 

480 volt systems

1,500 volts all modes

 

 

ORDERING INFORMATION

 

 

 

 

Building A Model Number: LPM 1 2 3

 

 

1: Nominal Voltage Requirements

2: System Configuration

3: Surge Current Capacity

Nominal Voltage Requirements

Model ID

System Configuration

Model ID

L-N

L-L

L-G

120

 

 

N or L

120

N/A

........120

Single (2 Wire + Gnd)

120

208

.......120

120

Split (3 Wire + Gnd)

S

120

240

........240

120

Wye (4 Wire + Gnd)

Y

N/A

208

........208

208

Delta Hi-Leg (4 Wire + Gnd)

H

230

400

........230

230

Delta (3 Wire + Gnd)

D

N/A

240

........240

240

 

 

 

277

480

........277

277

 

 

 

N/A

400

........400

400

 

 

 

N/A

480

........480

480

 

 

 

Surge Current Capacity

Model ID

Surge Current Capacity

Model ID

160 kA/Phase

160

100 kA/Phase

100 – 2

(L-N: 80 kA + L-G: 80 kA; N-G: 80 kA)

 

(L-N: 100 kA; N-G: 100 kA)

 

PANEL I.D.

MODEL NUMBER(S)

Job Name_______________________

Model# _________________________

Date ___________________________

Qty ____________________________

Quote# _________________________

Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229

 

Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169

 

EMAIL: info@control-concepts.com • Web Site: www.Liebert.com

82246 Rev 0

Page 1
Image 1