Calculite® HID Lensed Wall Wash C6P38MHL

Calculite® HID Lensed Wall Wash C6P38MHL

Page 1 of 2

-1/8" (486mm)

 

 

15" (381mm)

19

 

 

15" (381mm)

20" (508 mm) to 30" (762 mm)

10-5/8"

(270 mm)

20-1/4" (514 mm)

Top View

(Electronic Ballast)

20" (508 mm) to 30" (762 mm)

10-5/8"

(270 mm)

22-1/8" (562 mm)

Top View

(Magnetic Ballast)

19-5/8" (498 mm)

10

107/8"

(276 mm)

C

5/8" (16 mm)

6" Aperture, PAR38/PAR30 Ceramic Metal Halide, Lensed

5

8

1

2

4

3

6

9

7

Vertical Adjustment: 3/4" (25 mm) to 2 7/8" (73 mm)

5-3/4" (146 mm) Dia.

 

 

 

1 1/8" (29 mm) max.

 

 

 

7-7/8" (181 mm) Dia.

 

 

 

 

 

 

Ceiling Thickness

 

 

 

 

 

 

 

 

 

Ceiling Cutout: 6 9/16" (167mm) Dia.

Reflector Trim

 

Frame-In Kit
Lamp (Ceramic MH)

C6P38MHL CLW

Specular Clear White Painted Flange.

C6A70P38E1

Electronic 120V

70W

PAR38 Wide Flood

CLP

Specular Clear Matching Flange.

C6A70P38E2

Electronic 277V

70W

PAR38 Wide Flood

CCDW

Comfort Clear Diffuse, White Painted Flange.

C6A10P38E1

Electronic 120V

100W

PAR38 Wide Flood

CCDP

Comfort Clear Diffuse, Matching Flange.

C6A10P38E2

Electronic 277V

100W

PAR38 Wide Flood

CCZW

Champagne Bronze, White Painted Flange.

 

Magnetic 120V/277V

70W

PAR38 Wide Flood

CCZP

Champagne Bronze, Matching Flange.

 

Magnetic 120V/277V

100W

PAR38 Wide Flood

 

 

 

 

 

 

Features

1.Reflector Trim: Low brightness,anodized aluminum; integral flange in painted white or polished to match inside of cone.

2.Directional Spread Lens: High temperature, tempered glass. Precisely fits onto cone; replaceable.

3.Kick Reflector: 0.040” (16 ga.) aluminum. Clear anodized “Kick” reflector with directional spread lens distributes light smooth for vertical surface wall washing.

4.Socket: Medium base porcelain socket with nickel plated screwshell, pulse-rated

5.Frame Housing: Steel, 0.029" (22-Ga.), matte black finish.

6.Frame Vertical Adjustment Mechanism: Accommodates mounting to virtually any ceiling system using pre-installed mounting bars, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be pre-set prior to installation. Final adjustment can be made from below from inside fixture.

7.Mounting Bars: Galvanized steel, 0.048" (18-ga.), pre-installed telescoping bars extend to 30" long and lock securely into position. Built-in locking tabs provide positive attachment to common T-bar systems. Self-centering feature simplifies installation in 24" O.C. grid systems. Attaches to steel or wood joists without accessories.

8.Retention Springs: Rust resistant springs secure trim for quick, tool-less installation.

9.Ballast / Cover Assembly: Accessible from below and removable without tools for inspection and ballast replacement .

10.Junction Box: 0.059" (16-ga.) galvanized steel. UL listed for 8 No. 12 AWG, 90°C through branch circuit conductors. Allows inspection from below.

11.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do Not install insulation above nor within 3” (76mm) of any part of the luminaire.

Electrical

Electronic Ballast: 120V or 277V, 50/60 Hz. Electronic, encased, high power factor, T.H.D. <15%, thermally and transient protected, RMI/RFI complies with FCC part 18 non-consumer limits, shut-down circuit at end of lamp life, sound rating "A", -5° F minimum starting temperature, Type 1 Outdoor rating.

Electrical (Cont.)

Ballast

ANSI Code

Voltage

Max Amps

Input Watts

70W MH

M98/M143

120/277

0.67/0.28

78

100W MH

M90/M140

120/277

0.90/0.43

110

Magnetic Ballast: 120V/277V Dual Voltage, 60HZ Encased and potted, H8-HPF Circuit type, high power factor, sound rating “B”, -20° F minimum starting

temperature, type 1 outdoor rating.

 

 

Ballast

ANSI Code

Voltage

Max Amps

Input Watts

70W MH

M98/M143

120/277

1.90/0.80

94

100W MH

M90/M140

120/277

2.40/1.10

125

Options and Accessories

Fuse (magnetic ballast): Add suffix F1 or F2 to FIK (F1=120V F2=277V)

Chicago Plenum: Consult Factory.

Labels

UL (Suitable for Damp Locations), CSA (magnetic ballast only), I.B.E.W.

Job Information

Type:

Job Name:

Cat. No.:

Lamp(s):

Notes:

Lightolier a Genlyte companywww.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

© 2006 Genlyte Group LLC • B0406