Lightolier CFA2GPF254 Page 2 of, Ordering Information, Options/Accessories, Specifications, Type

Models: CFA2GPF228 CFA2GPF254

1 2
Download 2 pages 56.62 Kb
Page 2
Image 2
Coffaire II Recessed Fluorescent CFA2GPF228 or 254
<10THDI
P †
PG ††
PG ††
WA

Coffaire II Recessed Fluorescent CFA2GPF228 or 254

Page 2 of 2

Direct/Indirect – 2' x 4' with Perforated Basket Air Supply and Return, 2 Lamp T5

Model No. CFA2GPF228120WA

LER = FP - 57.2 IW - 54.9 BF - 0.93 Comparative yearly lighting energy cost per

1000 lumens = $4.20

Report Number: G2004258

Catalog Number: CFA2GPF228120WA

Lamps: F28T5

Luminaire: Coffaire direct/indirect with perforated basket

Ballast: WA

Report is based on 2600 Lumens per lamp. Efficiency: 65.0%

CIE Type-Direct-Indirect

 

 

 

 

Plane:

 

 

 

 

0-Deg

 

90-Deg

Spacing Criteria:

 

 

1.2

 

 

1.3

Shielding Angles:

 

 

55

 

 

65

Plane:

 

 

 

 

0-Deg

 

90-Deg

Luminous Length:

 

46.800

 

22.800

COEFFICIENTS OF UTILIZATION –

 

 

ZONAL CAVITY METHOD. EFFECTIVE

 

FLOOR CAVITY REFLECTANCE 0.20

 

 

 

 

 

 

 

 

 

 

 

RC

 

80

 

 

50

 

 

30

 

RW

70

50

30

50

30

10

50

30

10

01

71

68

65

64

62

60

61

59

58

02

64

59

55

55

52

49

53

51

48

03

59

52

46

49

45

41

47

43

40

04

54

46

40

43

39

35

42

38

34

05

49

41

35

39

34

30

37

33

30

06

45

37

31

35

30

26

34

29

26

07

42

33

27

32

27

23

31

26

23

08

39

30

25

29

24

21

28

24

20

09

36

28

22

27

22

19

26

22

18

10

34

26

20

25

20

17

24

20

17

LUMINANCE DATA IN CANDELA/SQ. METER

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG. 45-DEG. 90-DEG.

45

1466.

1672.

1807.

55

1344.

1673.

1848.

65

1144.

1636.

1690.

75

915.

1156.

1116.

85

533.

566.

566.

CANDELA DISTRIBUTION

 

0.0

45.0

90.0

FLUX

0

1151

1151

1151

 

5

1143

1146

1150

109

15

1091

1108

1125

313

25

999

1038

1076

479

35

871

940

997

586

45

714

814

880

622

55

531

661

730

578

65

333

476

492

441

75

163

206

199

213

85

32

34

34

40

90

2

2

2

 

 

 

 

 

 

ZONAL LUMEN SUMMARY

ZONE

LUMENS

% LAMP

% FIXT

00-030

901

17.3

26.6

00-040

1487

28.6

44.0

00-060

2687

51.7

79.4

00-090

3382

65.0

100.0

90-180

0000

0.0

000.0

00-180

3382

65.0

100.0

Model No. CFA2GPF254120PG

LER = FP - 50.7 IW - 123.2 BF - 1.00 Comparative yearly lighting energy cost per

1000 lumens = $4.73

Report Number: G2004261

Catalog Number: CFA2GPF254120PG

Lamps: FP54/835

Luminaire: Coffaire direct/indirect with perforated basket

Ballast: QT2X54/120

Report is based on 4400 Lumens per lamp. Efficiency: 70.8%

CIE Type-Direct-Indirect

 

 

 

 

Plane:

 

 

 

 

0-Deg

 

90-Deg

Spacing Criteria:

 

 

1.2

 

 

1.3

Shielding Angles:

 

 

55

 

 

65

Plane:

 

 

 

 

0-Deg

 

90-Deg

Luminous Length:

 

46.920

 

22.920

COEFFICIENTS OF UTILIZATION –

 

 

ZONAL CAVITY METHOD. EFFECTIVE

 

FLOOR CAVITY REFLECTANCE 0.20

 

RC

 

80

 

 

50

 

 

30

 

RW

70

50

30

50

30

10

50

30

10

01

77

74

71

69

67

65

66

65

63

02

70

64

59

60

57

53

58

55

52

03

64

56

50

53

48

44

51

47

44

04

58

50

43

47

42

348

45

41

37

05

53

44

38

42

37

32

40

36

32

06

49

40

33

38

32

28

37

32

28

07

46

36

30

34

29

25

33

28

25

08

42

33

27

31

26

22

30

26

22

09

40

30

24

29

24

20

28

23

20

10

37

28

22

27

22

18

26

21

18

 

 

 

 

 

 

 

 

 

 

LUMINANCE DATA IN CANDELA/SQ. METER

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG. 45-DEG. 90-DEG.

45

2759.

3032.

3246.

55

2612.

3044.

3326.

65

2352.

2993.

3085.

75

1798.

2160.

2076.

85

1041.

1108.

1075.

CANDELA DISTRIBUTION

 

0.0

45.0

90.0

FLUX

0

2082

2082

2082

 

5

2069

2073

2078

197

15

1986

2006

2035

568

25

1834

1885

1947

871

35

1621

1711

1803

1072

45

1354

1488

1593

1143

55

1040

1212

1324

1071

65

690

878

905

828

75

323

388

373

401

85

63

67

65

78

90

0

0

0

 

ZONAL LUMEN SUMMARY

ZONE

LUMENS

% LAMP

% FIXT

00-030

1636

18.6

26.3

00-040

2708

30.8

43.5

00-060

4921

55.9

79.0

00-090

6229

70.8

100.0

90-180

0000

00.0

000.0

00-180

6229

70.8

100.0

Ordering Information

Explanation of Catalog Number. Example: CFA2GPF228120WA

 

 

 

 

 

A

 

2

 

 

G

 

 

Coffaire II:

 

 

 

 

 

 

 

 

 

 

 

 

 

Body Style:

Fixture

Ceiling

Type:

 

Direct/

A = Air Supply

Width

Standard Grid

 

Indirect:

 

and Return

 

 

 

 

 

 

 

 

Recessed

 

 

 

 

 

 

 

 

 

 

 

with Perforated

 

 

 

 

 

 

 

 

 

 

 

Mesh Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Coffaire II

 

 

 

 

 

 

 

 

CF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN

 

For NYC Code – Local 3 Manufactured

 

 

 

 

P

Perforated

Lamp

Shield

F

Flat

White

Reflector

2

Lamp

 

 

 

Lamp:

Quantity

(By Others)

2=2 Lamp

28=28W T5

 

54=54W T5

 

(Nominal 48")

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage:

 

 

 

 

Options:

120, 277 or

 

 

 

Add appropriate

UNV=120-277

 

 

 

suffix to catalog

 

 

 

 

 

 

 

no., ie: (GLR)

 

 

 

Ballast

Type:

1-2 Lamp 28W Elec. T5

1-2 Lamp 28W Elec. T5

1-2 Lamp 54W Elec. T5

Linear T5 Instant Start

less than 10THD,

57.5Input Watts,

0.93Ballast Factor

†Instant Start (120, 277 or UNV) ††Program Rapid Start (UNV only)

Options/Accessories

Optional supply air slot cover: Order Catalog Number: CACS-4.

Fusing: Internal fast blow fusing: SUFFIX: GLR.Internal slow blow fusing: SUFFIX: GMF.Drywall Kit: Order Catalog Number: FK92X4.Electrical Wiring Options: Consult factory.Chicago Plenum: SUFFIX: C.Dust Shield: See Folio Number: OA50-20

Specifications

Performance: In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .66. To reduce glare the average brightness at 65° shall not exceed 2093 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 74.6%.

Materials: Chassis parts are die-formed code gauge steel.

Lamp Shield: 22 gauge steel perforated mesh lamp shield with white acrylic overlay.

Specifications (continued)

Finish: Chassis exterior – soft white post painted polyester powder. Cavity – soft white post painted polyester powder. Reflector – soft white post painted polyester powder, minimum 88% reflectance. Rust preventive undercoating. Lamp Shield –white.

Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations.

Labels: I.B.E.W./UL and ULc Listed.

 

Job Information

Type:

 

 

 

Lightolier a Genlyte company

www.lightolier.com

Technical Information: (978) 657-7600 • Fax (978) 658-0595

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish.

© 2007 a Genlyte company

Section 5/Folio M15-42

Page 2
Image 2
Lightolier CFA2GPF254 Page 2 of, Ordering Information, Options/Accessories, Specifications continued, Job Information