Page 2 of 2 | Linear Prismatic Lens, 55% Downlight, 45% Uplight |
| 48" Length 3 Lamp T5/T8, 96" Length 3 Lamp T5/T8 in Tandem |
LER = FP - 68.9 IW - 89.5 BF - 0.88 Comparative yearly lighting energy cost per
1000 lumens = $3.48
Report Number: G2005284
Catalog Number: EYS4LNFX332UNVH3
Lamps: F32T8/TL841
Luminaire:
Report is based on 2850 Lumens per lamp.
Efficiency: 81.5% |
|
|
|
|
|
| |||
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.2 |
|
| 1.3 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 48.000 |
| 9.000 | |||||
Height of Side: |
|
| 3.960 |
| 3.960 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 80 | 76 | 72 | 60 | 58 | 55 | 50 | 49 | 47 |
02 | 72 | 66 | 60 | 52 | 48 | 45 | 44 | 41 | 39 |
03 | 66 | 57 | 51 | 46 | 41 | 38 | 38 | 35 | 33 |
04 | 60 | 51 | 44 | 40 | 36 | 32 | 34 | 31 | 28 |
05 | 55 | 45 | 38 | 36 | 31 | 27 | 31 | 27 | 24 |
06 | 51 | 40 | 33 | 32 | 27 | 24 | 28 | 24 | 21 |
07 | 47 | 36 | 30 | 29 | 24 | 21 | 25 | 21 | 18 |
08 | 43 | 33 | 26 | 27 | 22 | 19 | 23 | 19 | 16 |
09 | 40 | 30 | 24 | 24 | 20 | 17 | 21 | 17 | 15 |
10 | 38 | 28 | 22 | 23 | 18 | 15 | 19 | 16 | 13 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. | |||
45 | 3781. | 3455. | 3663. |
55 | 3054. | 3224. | 2995. |
65 | 2243. | 2633. | 2432. |
75 | 1430. | 2203. | 2476. |
85 | 360. | 2013. | 2177. |
CANDELA DISTRIBUTION0 |
|
| ||
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 1317 | 1317 | 1317 |
|
5 | 1310 | 1256 | 1239 | 120 |
15 | 1266 | 1143 | 1136 | 329 |
25 | 1169 | 994 | 1076 | 484 |
35 | 1018 | 888 | 1116 | 599 |
45 | 807 | 859 | 1040 | 656 |
55 | 546 | 708 | 780 | 592 |
65 | 311 | 484 | 557 | 447 |
75 | 135 | 314 | 472 | 321 |
85 | 17 | 195 | 319 | 205 |
90 | 9 | 168 | 273 |
|
95 | 53 | 244 | 324 | 249 |
105 | 209 | 404 | 547 | 403 |
115 | 377 | 451 | 613 | 456 |
125 | 525 | 482 | 609 | 468 |
135 | 647 | 531 | 600 | 461 |
145 | 755 | 718 | 626 | 443 |
155 | 839 | 875 | 839 | 391 |
165 | 896 | 909 | 932 | 258 |
175 | 924 | 922 | 929 | 88 |
180 | 924 | 924 | 924 |
|
|
|
|
|
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
933 | 10.9 | 13.4 | |
1533 | 17.9 | 22.0 | |
2781 | 32.5 | 39.9 | |
3753 | 43.9 | 53.8 | |
1108 | 13.0 | 15.9 | |
1575 | 18.4 | 22.6 | |
2480 | 29.0 | 35.6 | |
3217 | 37.6 | 46.29 | |
6970 | 81.5 | 100.0 |
Model No. EYS4LNFX354UNVPV
LER = FP - 69.9 IW - 175.5 BF - 1.0 Comparative yearly lighting energy cost per
1000 lumens = $3.43
Report Number: G2005296
Catalog Number: EYS4LNFX354UNVP5
Lamps: FP54/835
Luminaire:
Report is based on 4400 Lumens per lamp.
Efficiency: 93.1% |
|
|
|
|
|
| |||
CIE |
|
|
|
| |||||
Plane: |
|
|
|
|
| ||||
Spacing Criteria: |
|
| 1.2 |
|
| 1.1 | |||
Shielding Angles: |
|
| 90 |
|
| 90 | |||
Plane: |
|
|
|
|
| ||||
Luminous Length: |
| 48.000 |
| 9.000 | |||||
Height of Side: |
|
| 3.960 |
| 3.960 | ||||
COEFFICIENTS OF UTILIZATION – |
|
| |||||||
ZONAL CAVITY METHOD. EFFECTIVE |
| ||||||||
FLOOR CAVITY REFLECTANCE 0.200 |
| ||||||||
RC |
| 80 |
|
| 50 |
|
| 30 |
|
RW | 70 | 50 | 30 | 50 | 30 | 10 | 50 | 30 | 10 |
01 | 91 | 86 | 82 | 69 | 66 | 64 | 58 | 56 | 54 |
02 | 82 | 75 | 69 | 60 | 55 | 52 | 51 | 47 | 45 |
03 | 75 | 65 | 58 | 52 | 47 | 43 | 44 | 40 | 37 |
04 | 68 | 58 | 50 | 46 | 41 | 36 | 39 | 35 | 32 |
05 | 63 | 51 | 43 | 41 | 35 | 31 | 35 | 31 | 27 |
06 | 58 | 46 | 39 | 37 | 31 | 27 | 32 | 27 | 24 |
07 | 53 | 41 | 34 | 33 | 28 | 24 | 29 | 24 | 21 |
08 | 49 | 37 | 30 | 30 | 25 | 21 | 26 | 22 | 18 |
09 | 46 | 34 | 27 | 28 | 22 | 19 | 24 | 20 | 17 |
10 | 43 | 31 | 24 | 26 | 20 | 17 | 22 | 18 | 15 |
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. | |||
45 | 7371. | 6181. | 6664. |
55 | 6109. | 6175. | 5610. |
65 | 4456. | 5146. | 4476. |
75 | 3009. | 4182. | 4993. |
85 | 1080. | 3933. | 4607. |
CANDELA DISTRIBUTION0
| 0.0 | 45.0 | 90.0 | FLUX |
0 | 2482 | 2492 | 2492 |
|
5 | 2465 | 2253 | 2157 | 215 |
15 | 2383 | 2002 | 1935 | 576 |
25 | 2158 | 1695 | 1792 | 836 |
35 | 1859 | 1495 | 1932 | 1044 |
45 | 1573 | 1537 | 1892 | 1184 |
55 | 1092 | 1356 | 1461 | 1104 |
65 | 618 | 946 | 1025 | 847 |
75 | 284 | 596 | 952 | 629 |
85 | 51 | 381 | 675 | 423 |
90 | 15 | 310 | 529 |
|
95 | 100 | 396 | 502 | 423 |
105 | 394 | 688 | 1070 | 731 |
115 | 689 | 778 | 936 | 748 |
125 | 927 | 794 | 1027 | 793 |
135 | 1117 | 828 | 963 | 764 |
145 | 1281 | 1239 | 963 | 735 |
155 | 1403 | 1474 | 1442 | 662 |
165 | 1489 | 1502 | 1542 | 427 |
175 | 1529 | 1523 | 1533 | 145 |
180 | 1528 | 1528 | 1528 |
|
ZONAL LUMEN SUMMARY
ZONE | LUMENS | % LAMP | % FIXT |
1627 | 12.3 | 13.2 | |
2671 | 20.2 | 21.7 | |
4959 | 37.6 | 40.4 | |
6857 | 51.9 | 55.8 | |
1902 | 14.4 | 15.5 | |
2696 | 20.4 | 21.9 | |
4195 | 31.8 | 34.1 | |
5429 | 41.1 | 44.2 | |
12286 | 93.1 | 100.0 |
Ordering Information
Explanation of Catalog Number. Example: EYS4LNFX332UNVH3
EY |
|
|
|
|
|
| LN |
| F | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
X
3
S=Solid | Fixture | LN=Linear | Finish: | |
Suspended/ | Sides | Length: | Prismatic | F= Flat |
Surface | P=Perforated | 4=48" | Lens | White |
Fluorescent | Sides | 8=96" |
|
|
Luminaire |
|
|
|
|
Options/Accessories
Stem and Canopy Sets: Suspends fixture 6", 12", 18" or 24" from surface.
Catalog Number: ASC6 CSP (6"), ASC12 CSP (12"), ASC18 CSP (18"), ASC 24 CSP (24").
Fusing: Internal fast blow fusing: SUFFIX: GLR. Internal slow blow fusing: SUFFIX: GMF.
Emergency Pack:
charger and inverter. SUFFIX: LP400 (T8). LP550 (T5).
Cable Hangers: Adjustable
X= No Top | Lamp |
Reflector | Quantity: |
| 3=3 Lamp |
| 3 Lamps in |
| Tandem for |
| 96" Units |
Lamp Type: | Voltage: |
|
|
| |
| Options: | ||||
(By Others) | 120, 277 or |
| Add appropriate | ||
32=T8 |
| suffix to catalog | |||
28=T5 |
|
| no., ie: (GLR) | ||
54=T5 | Ballast Type: |
|
| ||
(Nominal 48") | <20THD | <10THD | |||
|
| ||||
SO * | HI * | ||||
SO * | HI * | ||||
O3 * | H3 * | ||||
– | PI † | ||||
– | PI † | ||||
– | †PU †† | ||||
– | †PG †† | ||||
– | †PG †† | ||||
LOL T8 Dimming | PS * | – | |||
Other dimming options. Consult factory. |
|
|
†*Instant Start Standard
††Instant Start (120V or 277V only) ††Program Rapid Start (UNV only)
NOTE:
For T8 UNV, you must use HI, H3 Ballast Code.
Single Cable, Straight Cord and Canopy: Catalog Number: WCC60**.
Single Cable, Coil Cord and Canopy: Catalog Number: WCCC60**.
Chain Hanger Kits: Catalog Number: AH5 CSP.**Cord,
Specifications (continued)
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed.
Specifications
Materials: Housing is
Fixture Ends: 18 gauge cold rolled steel.
Lens: Linear Prismatic.
Side Reflectors: Solid 22 gauge cold rolled steel.
Finish: Post painted white acrylic baked enamel.
Job Information | Type: |
|
|
Lightolier a Genlyte company | www.lightolier.com |
Technical Information: (978) | |
631 Airport Road, Fall River, MA 02720 • (508) | |
We reserve the right to change details of design, materials and finish. | |
© 2005 a Genlyte company | Section 5/Folio |