Lightolier IS:EMBW B.Operation, C.Maintenance, Is Embw, LIGHTOLIER a GENLYTE THOMAS company

Models: IS:EMBW

1 2
Download 2 pages 50.31 Kb
Page 2
Image 2
B.OPERATION

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING LUMINAIRE

This luminaire is intended for installation in accordance with the National Electrical Code and local regulations. To assure full compliance with local codes and regulations, check with your local electrical inspector before installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.

Retain these instructions for maintenance reference.

INSTRUCTION SHEET NO.

IS:EMBW

A0402

Page 2 of 2

INSTRUCTIONS FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT

EMERGENCY LIGHTING DECORATIVE WALL LUMINAIRES

INDICATOR

LIGHT

WIRING DIAGRAM A

 

 

 

 

 

 

 

-BROWN

VIOLET+

 

 

(2-Lamp 18W Quad Tube

 

 

Pre-Wired for 120V or 277V)

 

 

 

 

 

 

(ONE EMERGENCY LAMP ON)

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: FOR UNSWITCHED CIRCUIT, CONNECT

 

 

 

 

 

 

120V OR 277V EMERGENCY PACK HOT

 

 

 

 

 

 

LEAD TO AC BALLAST HOT LEAD.

RED

 

 

 

INVERTER

 

EMERGENCY

CONNECTOR

 

BALLAST

 

 

 

 

 

 

 

 

WHITE

CAP UNUSED

LEAD

120V (BLK) OR

277V (ORG)

120V (BLK) OR 277V (ORG) (COM) WHITE

BLUE/WHITE

BLUE

YELLOW

YEL/BLK

RED

HOT (UNSWITCHED)

SKT

WHITE

TEST BLK SWITCH

BLK

RED

COM

 

 

 

 

 

 

HOT (SWITCHED OR UNSWITCHED)

 

 

 

GRD

TO LUMINAIRE GROUNDS

 

 

 

 

AND SUPPLY GROUND

 

 

 

GREEN

 

 

 

 

 

BLACK

 

 

 

 

 

WHITE

 

 

 

 

 

BLUE

 

 

 

 

 

BLUE

AC

 

 

 

 

YEL A

BALLAST

 

 

 

 

 

 

 

 

 

YEL B

 

SKT

 

 

 

RED

 

 

 

RED

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B.OPERATION

When AC power is applied, the charging indicator light is illuminated indicating that the battery is being charged. When the power fails, the emergency lighting ballast automatically switches to emergency operation, keeping one lamp illuminated at reduced output for 90 minutes.

C.MAINTENANCE

Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended:

1.Visually inspect the charging indicator light monthly. It should be illuminated.

2.Test the emergency operation of the luminaire once every 3 months. One lamp should operate at reduced output.

3.Conduct a 90 minute discharge test at least once a year or more if required by local ordinance. One lamp should operate at reduced output for 90 minutes.

LIGHTOLIER a GENLYTE THOMAS company.

631 Airport Road, Fall River, MA 02720

Page 2
Image 2
Lightolier IS:EMBW B.Operation, C.Maintenance, Is Embw, Emergency Lighting Decorative Wall Luminaires