Operation of the cascade

User’s Information Manual

4SMART SYSTEM control module

Status Display Screens (cont’d)

Operation of the cascade

The boiler designated as the Leader will have two additional display screens that can be viewed. These screens will provide information regarding the operation of the Cascade. Each screen will contain two viewable items. The following is a description of the individual items and what they can display:

Screen

 

Display shows:

Description

 

 

Cas: Off

The Leader control has been turned off by the Enter/Reset button on

 

 

the Smart System display.

 

 

 

 

 

 

 

 

 

Cas: Standby

The Leader boiler has not received a call for heat from a remote

 

 

thermostat.

 

 

 

 

 

 

 

 

 

Cas: 127.4F (130)

The Cascade is now active. The system supply temperature will be

 

 

displayed. The Cascade set point will be displayed in parenthesis.

 

 

 

 

 

 

 

 

 

Cas: Setpoint Met

The Cascade has met the water temperature set point, but is still

 

 

receiving a call for heat from a remote thermostat.

 

 

 

 

 

 

 

 

 

Cas: No Members

The Leader control could not detect any Member controls to

#9

 

participate in the Cascade.

 

 

 

 

 

 

 

 

Cas: S6 Not Present

The system supply sensor is not connected to the Leader boiler.

 

 

 

 

 

 

PMP: Off

The Leader control has not received a call for heat from a remote

 

 

thermostat and has not powered the system pump.

 

 

 

 

 

 

 

 

 

PMP: On

The Leader control has received a call for heat from a remote

 

 

thermostat and has powered the system pump.

 

 

 

 

 

 

 

 

 

PMP: Delay

The system call for heat has been satisfied and the system pump is

 

 

running for a fixed time to remove any residual heat.

 

 

 

 

 

 

 

 

Press the Next ￿ arrow key on the SMART SYSTEM display to access Screen #10.

 

 

 

 

#10

 

The first percentage shows the firing rate that is being sent to the last

Cas Pow: ***% ***%

boiler called on. The second percentage shows the total power

 

available to the Cascade.

 

 

 

Shows the number of boilers connected to the Cascade. The Leader

 

is designated as 0. Members will be designated 1 - 7. If a “-“ is used

Present: 01234567

in place of a number, that boiler is either not connected, or in a

lockout mode and not available for the Cascade. If a “d” is used in

 

Example:

place of a number, that boiler is handling a DHW demand and is not

available for the Cascade. If the number is flashing, then that boiler

Present: 23----d1

is providing heat to the Cascade. As the lead boiler is changed from

 

 

day to day, that boiler’s address will be shown first in the string of

 

numbers. In the example, boilers 0 - 3 are present, boiler 2 is the lead

 

boiler, and boiler 0 is heating an indirect DHW tank.

Press the Next ￿ arrow key on the SMART SYSTEM display to roll back to Screen #1. At any point if you wish to access an earlier screen, press the Previous ￿ arrow key on the SMART SYSTEM display.