PIPING DIAGRAM | TWO |
|
|
| COLD WATER | |
| SUPPLY | |
| LOCHINVAR | |
| WATER HEATERS | |
| OUTLET | |
BUILDING | RELIEF | |
VALVE | ||
HOT WATER | ||
INLET | ||
SUPPLY | ||
| ||
OUTLET | ||
STORAGE |
| |
TANKS |
|
DRAIN
Gray shaded area represents common manifold piping. | BUILDING |
| RETURN |
COMMON WATER MANIFOLD SIZE FOR MULTIPLE WATER HEATER INSTALLATION
Pipe sizing chart provides minimum pipe size for common manifold piping to ensure adequate flow. | |||
|
|
|
|
NUMBER OF | COMMON MANIFOLD SIZE | NUMBER OF | COMMON MANIFOLD SIZE |
UNITS | (Min.) | UNITS | (Min.) |
CW |
| CW |
|
1 | 2” | 1 | |
2 | 3” | 2 | 4” |
3 | 3 | 4” | |
4 | 4” | 4 | 5” |
5 | 5” | 5 | 6” |
6 | 5” | 6 | 6” |
|
|
|
|
This illustration is for concept only and should not be used for any actual installation without engineering | LIT0451 |
or technical advice from a licensed engineer. All necessary equipment may not be illustrated. |
L E G E N D
FULL PORT BALL VALVE
SYSTEM
PUMP
SYSTEM
RELIEF VALVE
TEE
ELBOW
UNION
EXPANSION
TANK
CHECK VALVE
THERMOMETER
REDUCING
TEE
REDUCING
TEE
Lochinvar D E S I G N E R ’ S G U I D E C O P P E R - F I N W A T E R H E A T E R | A5 |