Lochinvar E B N 150 Input, Efficiency+ Boiler Dimensions & Specifications, Standard Features

Models: E B N 150

1 2
Download 2 pages 48.63 Kb
Page 2
Image 2
Efficiency+® Boiler Dimensions & Specifications

Efficiency+® Boiler Dimensions & Specifications

 

Efficiency+ Boiler

 

Dimensions & Specifications

 

 

 

 

 

Input

 

Heating

Net

 

 

 

 

 

 

 

Model

Max

AFUE
Capacity
I=B=R

 

 

 

 

Gas

Vent

Shipping

Number

MBH

%

MBH

MBH

B

D

E

G

Conn.
Size

Weight

EBN150

150

83.2

129

112

19-3/4”

16”

7-1/4”

11-3/4”

3/4”

5”

245

EBN200

200

83.1

170

148

23-3/4”

20”

9-1/4”

11-3/4”

3/4”

5”

265

EBN250

250

83.2

218

190

27-1/2”

23-3/4”

11”

11-3/4”

3/4”

6”

290

EBN300

300

84.0

252

219

31-1/4”

27-1/2”

13”

11-3/4”

3/4”

6”

310

Notes: Change ‘N’ to ‘L’ to denote L.P. gas models

 

Electrical Requirements: 120 VAC / 2 AMP

Water connections are 1-1/2” NPT

 

Net ratings based on piping and pick-up allowance of 1.15

Performance data based on manufacturer test results.

 

 

 

Standard Features

 

 

 

 

 

Available Firing Systems

84% AFUE

Two Stage Firing

Sealed Combustion Chamber

Stainless Steel Burners

Low NOx Operation Exceeds the most Stringent Air Quality Requirements

ASME Copper Finned Tube Heat Exchanger

160 PSI Working Pressure

Gasketless Heat Exchanger Design

Automatic Reset High Limit

Loch-Heat Ceramic Tile Combustion Chamber

Hot Surface Ignition

ASME Pressure Relief Valve

24 Volt Control System

Pump Relay

10 Year Limited Warranty on Heat Exchanger

(See warranty for details)

Optional Equipment

Adjustable High Limit w/ Manual Reset

Alarm Bell

Cupro-Nickel Heat Exchanger

Flow Switch

Indoor/Outdoor Reset

Manual Reset Low Water Cut-Off w/test

MP2 Sequencer

Stack Frame

Pump Delay w/ Freeze Protection

M9 Hot Surface Ignition with Electronic Supervision (Standard)

M7 California Code

For Ease In Ordering

By Model Number

E

B

N

150

Efficiency+

Boiler

Natural

Input

 

 

 

 

 

 

Gas

 

This is a 150,000 Btu/hr

natural gas Efficiency+ boiler. Registered Under U.S. Patent #5,989,020

Venting Options

Conventional

Vents into conventional flue or vent breaching using Type B double wall vent.

**Outdoor Vent Kit

Use when indoor space is a problem or if outdoor location gives better access.

**E+ DirectAire Vent with Sidewall Inlet

Draws fresh combustion air from an outside wall horizontally, and vents combustion by-products through a vertical flue.

Direct Vent Vertical

Draws fresh combustion air from outside, and vents combustion by-products through a vertical flue.

**Direct Vent Horizontal Draws fresh combustion air from outside, then vents by-products through a side wall.

**Requires factory supplied vent kit.

Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000

EBN-04Revised EBN-04 9/08)

www.Lochinvar.com

FG-5M-3/10-Printed In U.S.A.

Page 2
Image 2
Lochinvar E B N 150 Input, Efficiency+ Boiler Dimensions & Specifications, Standard Features, Available Firing Systems