Including
aBuilt-in Cascading Sequencer!
InIn commerciacommerciall buildingsbuildings requrequiringiring aa multiple boiler system, modulating operationoperation ofof individindividualua l unitsunits shshouldould be sequenced so that the system functions as an integrated whole.
SMART SYSTEM includes a built-in cascading sequencer for up to 8 KNIGHT XL units. This eliminates the initial cost and labor required with installation of a separate sequencer. And, because it’s engineered specifically for Lochinvar boilers, it removes any uncertainty about using a ”third-party” sequencer, to ensure precise, dependable cascading operation.
When utilizing the built-in cascading sequencer, KNIGHT XL boilers communicate through a simple 2-wire daisy chain connection. On demand, one boiler in the system functions as the leader, and modulates with demand to capacity. The additional load then ”cascades” to the second boiler, which fires and modulates to meet added demand via a patented process to match system load and reduce equipment short cycling.
CascadingCascading continuescontinues asas additionaladditional boilboilersers fifirere iinn sequencesequence,, ununtiltil allall units are in operation or demand is satisfied. When demand drops, the patented cascading process reverses, with the precision, control and performance you expect from Lochinvar.
SMART SYSTEM also controls Lead-Lag Rotation. Every 24 hours the lead boiler role is shifted to the next unit in the sequence. This rotation ensures long life by distributing ”lead-lag” runtimes equally over each unit in the system.