Lochinvar PUMP-REC-05 REV B specifications Recommendation PUMP-Rec-05, Pump Specifications

Models: PUMP-REC-05 REV B

1 2
Download 2 pages 305 b
Page 2
Image 2
Recommendation

PUMP

Recommendation

PUMP-Rec-05

PUMP RECOMMENDATION FOR COPPER-FIN 0986-2066 WATER HEATER

Pump Specifications

Part No.

HorsePower

Flanges

Valute Material

Flange Material

Vendor

ARM3024PAB

1/2

2-1/2"

Brass

Brass

Armstrong

Vendor Product Series

2B1050

Orientation

Horizontal

Installation Specifications

 

Recommended for

 

Based on

Pump

Model Numbers

Maximum GPM

Installation Type

 

Copper-Fin Wtr Htr, CW(N,L) 0986-2066

90 GPM

Single Water Heater piped to Single Storage Tank

ARM3024PAB

Based on

Based on

 

 

Minimum Pipe Diameter

Connecting piping

 

 

2-1/2"

Maximum 45 feet straight pipe with 6-Elbows, 2-Unions,2-Ball Valves and 1-Cold Water Inlet Tee

IMPORTANT: Read the Copper-fin 495-2065 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump-REC-All Pumps” for alternate pumps and pump curves.

19-A1/2”

16”C

OIL PORT

11-B1/2”

D

2

Page 2
Image 2