LST 2251EIS specifications Safety Barrier Y72221, Protocol Interface IST200, Specifications

Models: 2251EIS

1 2
Download 2 pages 5.42 Kb
Page 2
Image 2
Safety Barrier Y72221

Safety Barrier Y72221

The Safety Barrier Y72221 (fi g. B) is used for intrinsi- cally safe electric circuits. The built-in zener barrier and the safe galvanic isolation allow the connecton of fi re

detectors in hazardous areas. Due to the galvanic isola- tion, the earth leakage monitoring can remain activated in the fi re detection control panel.

Specifications

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia IIC T5

Operating voltage

Supply through the detector line voltage

Ambient temperature

-20°C to +60°C

Dimensions W × H × D

20 × 110 × 107.5 (mm)

Mounting

TS35 DIN rail

Colour

green

Weight

100g

Approval

BASEEFA Nr.: BAS00ATEX7087

Order number

228006

Order name

Safety Barrier/Anal./200/SS Y72221

Protocol Interface IST200

The Protocol Interface IST200 (fi g. C) serves for the design of an intrinsically safe electric circuit in ADM loop technology. It allows the bidirectional data traffi c between fi re detection control panel and fi re detectors in hazardous areas via an ADM loop with System Sen-

sor/200 protocol. The interface is always used toge- ther with the Safety Barrier Y72221. The Surface Moun- ting Box SMB500 is required for mounting the protocol interface.

Specifications

Ignition protection

intrinsically safe

Operating voltage

Supply through loop voltage

Current consumption at 24V

14mA

Ambient temperature

0°C to +60°C

Relative humidity

5 – 95% (no condensation)

Dimensions W × H × D (without attaching sheet)

70 × 70 × 32 (mm)

Weight

155g

Order number

228007

Order name

Protocol Interface/Anal./200/SS IST200