Safety Barrier Y72221
The Safety Barrier Y72221 (fi g. B) is used for intrinsi- cally safe electric circuits. The
detectors in hazardous areas. Due to the galvanic isola- tion, the earth leakage monitoring can remain activated in the fi re detection control panel.
Specifications
Ignition protection | intrinsically safe |
Ex classifi cation | EEx ia IIC T5 |
Operating voltage | Supply through the detector line voltage |
Ambient temperature | |
Dimensions W × H × D | 20 × 110 × 107.5 (mm) |
Mounting | TS35 DIN rail |
Colour | green |
Weight | 100g |
Approval | BASEEFA Nr.: BAS00ATEX7087 |
Order number | 228006 |
Order name | Safety Barrier/Anal./200/SS Y72221 |
Protocol Interface IST200
The Protocol Interface IST200 (fi g. C) serves for the design of an intrinsically safe electric circuit in ADM loop technology. It allows the bidirectional data traffi c between fi re detection control panel and fi re detectors in hazardous areas via an ADM loop with System Sen-
sor/200 protocol. The interface is always used toge- ther with the Safety Barrier Y72221. The Surface Moun- ting Box SMB500 is required for mounting the protocol interface.
Specifications
Ignition protection | intrinsically safe |
Operating voltage | Supply through loop voltage |
Current consumption at 24V | 14mA |
Ambient temperature | 0°C to +60°C |
Relative humidity | 5 – 95% (no condensation) |
Dimensions W × H × D (without attaching sheet) | 70 × 70 × 32 (mm) |
Weight | 155g |
Order number | 228007 |
Order name | Protocol Interface/Anal./200/SS IST200 |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|