LST specifications IS Optical Smoke Detector AOEX-55000-640, Specifications, ATEX certified

Models: AOEX-55000-640

1 3
Download 3 pages 20.06 Kb
Page 1
Image 1
Devices for Hazardous Areas

Devices for Hazardous Areas

for the Apollo/Discovery Loop

ADM loop technology with Apollo/Discovery protocol

Optical smoke detector

Thermal detector

Safety barrier with galvanic isolation

Protocol interface for communication with the fire detection control panel

ATEX certified

IS Optical Smoke Detector AOEX-55000-640

fi g. A

fi g. C

fi g. B

fi g. D

The addressable Intrinsically Safe Optical Smoke De- tector AOEX-55000-640 (fi g. A) uses the scattered light principle and was developed for the detection of smo- ke particles in hazardous areas. The smoke detector must always be connected via a safety barrier, which has been approved for this detector, and a protocol interface. Furthermore, the relevant country specifi c regulations always have to be observed.

The proven ADM loop technology with Apollo/Discovery protocol establishes a permanent communication be- tween the fi re detection control panel and the detector. That ensures a periodical function testing of the detec- tor. In the control panel all types of fi res are detected by continuously comparing fi re patterns.

Intelligent evaluation algorithms use the current condi-

tion of the sensing chamber to predict the likely time of the next maintenance. Thus the alarm threshold is automatically adjusted within the permissible range, de- pending on the contamination. With that, the constant response sensitivity of the detector is ensured for a long time.

The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is se- lected by means of a code card in the detector base. Therefore the detector can be changed without additi- onal tools.

The detector is inserted into the IS Detector Base ASEX- 45681-215 (not illustrated) and it can be protected against theft.

Specifications

Ignition protection

intrinsically safe

Ex classifi cation

EEx ia IIC T5

Operating voltage

Supply through loop voltage

Current consumption

typ. 340µA (quiescent)

Ambient temperature

-20°C to +40°C (no condensation or icing)

Relative humidity

0 – 95% (no condensation)

Dimensions ø × H

100 × 42 (mm)

Colour

white

Weight

100g

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

Ex-ApoDisc_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Page 1
Image 1
LST specifications IS Optical Smoke Detector AOEX-55000-640, Specifications, Devices for Hazardous Areas, ATEX certified