Devices for Hazardous Areas
for the Apollo/Discovery Loop
•ADM loop technology with Apollo/Discovery protocol
•Optical smoke detector
•Thermal detector
•Safety barrier with galvanic isolation
•Protocol interface for communication with the fire detection control panel
•ATEX certified
IS Optical Smoke Detector AOEX-55000-640
fi g. A
fi g. C
fi g. B
fi g. D
The addressable Intrinsically Safe Optical Smoke De- tector
The proven ADM loop technology with Apollo/Discovery protocol establishes a permanent communication be- tween the fi re detection control panel and the detector. That ensures a periodical function testing of the detec- tor. In the control panel all types of fi res are detected by continuously comparing fi re patterns.
Intelligent evaluation algorithms use the current condi-
tion of the sensing chamber to predict the likely time of the next maintenance. Thus the alarm threshold is automatically adjusted within the permissible range, de- pending on the contamination. With that, the constant response sensitivity of the detector is ensured for a long time.
The two LEDs with 360° visibility indicate the activated condition of the detector. The detector address is se- lected by means of a code card in the detector base. Therefore the detector can be changed without additi- onal tools.
The detector is inserted into the IS Detector Base ASEX-
Specifications
Ignition protection | intrinsically safe |
Ex classifi cation | EEx ia IIC T5 |
Operating voltage | Supply through loop voltage |
Current consumption | typ. 340µA (quiescent) |
Ambient temperature | |
Relative humidity | 0 – 95% (no condensation) |
Dimensions ø × H | 100 × 42 (mm) |
Colour | white |
Weight | 100g |
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • | |
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED |
|