Isolator Module

ISM1-3

Safe disconnection of a faulty loop section

For use in an Apollo/Discovery loop

Installation in commercial installation boxes or in the LST standard grid

Small design

Description

The Isolator Module ISM1-3 is used on the ADM loop with Apollo/Discovery protocol and disconnects the loop in the event of a short circuit of the loop connection.

Thereby only the loop elements located between two isolator modules are affected by the short circuit.

The Fire Detection Control Panels Series BC216 report the affected loop elements as faulty and operate the remaining loop sections, which are not faulty, from both ends of the loop, until the fault is removed.

Specifications

Operating voltage

Supply through loop voltage

Current consumption

max. 0.2mA

Ambient temperature

-5°C to +50°C

Dimensions L × W × H

70 × 24 × 15 (mm)

Weight

20g

Approval

VdS G296012

Order number

249029

Order name

Isolator Module/Anal./Apo ISM1-3

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

ISM1-3_DBL_LST_EN_0804.PDF • PAGE 1