LST LAB48 specifications field, to which it is directly connected, LED Display Field, Description

Models: LAB48

1 2
Download 2 pages 46.51 Kb
Page 1
Image 1
LED Display Field

LED Display Field

LAB48

48 freely programmable LED pairs

Indication of events and conditions of fire detection control panels Series BC216 or BC016

Installation in control panels Series BC216 or
LED Display Tableau LAT288
Different LED colors available

Individual labeling by means of inserted text labeling strips

Description

The LED Display Field LAB48 serves for the indication of the events of detectors, detector zones, actuations, transmitting devices, or alarming devices on fi re detec- tion control panels Series BC216 or BC016 as well as the events of fl ooding zones or extinguishing systems on extinguishing control panels Series LC216.

The LED Display Field is designed to be installed into

re detection control panels Series BC216 or into the LED Display Tableau LAT288:

• The LAB48 can be mounted into a fi re detection con- trol panel Series BC216 with display and operating

eld, to which it is directly connected.

The LED Display Tableau LAT288 can accommodate up to 3 LED Display Fields LAB48 and the Remote Tableau Drive Unit PTU288-1. Due to the actuation via the INFO bus, the LED Display Tableau is a universal remote tableau for all fi re detection control panels Se- ries BC216 and BC016 as well as the extinguishing control panel Series LC216.

48 LED pairs are arranged in two rows on the com- ponentry. Each LED pair can be freely assigned to the individual events. The left LEDs are intended for dis- playing the alarm or the activation, or for displaying a system condition, respectively. The right LEDs indicate the disablement or the fault condition of the assigned system component.

The LED Display Field is available in multiple versions with different LED colors for varying applications.

Each LED pair can be individually labeled by means of labeling strips which are inserted into the front foil of the case cover.

The componentry is shipped with the necessary ac- cessory for trouble-free mounting on the case cover of the fi re detection control panel or in the LED Display Tableau.

Specifications

Current consumption at 24V

typ. 2mA no active LED, +0.25mA per LED

Ambient temperature

-20°C to +60°C

Dimensions L × W × H

176 × 120 × 15 (mm)

Weight

60g

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

LAB48_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 

Page 1
Image 1
LST LAB48 specifications field, to which it is directly connected, Building Safety. Building Security, LED Display Field