LST M210E specifications Monitor Module, Description, Specifications

Models: M210E

1 2
Download 2 pages 34.24 Kb
Page 1
Image 1
Monitor Module

Monitor Module

M210E

ADM loop technology with System Sensor/200 protocol

One input with line-monitoring for wire breakage and short circuit

Status LED

Setting of module address via decadic rotary switches

Mounting in module box or by means of mounting base

Description

The addressable Monitor Module M210E serves for the line-monitored integration of contact detectors, such as manual call points, sprinkler system contacts or super- vising contacts, into the bidirectional communication on the ADM loop with System Sensor/200 protocol.

A status LED indicates the condition of the monitor module. Separate terminals enable the operation of the module with or without the integrated dual-isolator. Accessories for mounting on a wall, on a plate or on a DIN rail are available.

Specifications

Operating voltage

Supply through loop voltage

Current consumption

approx. 510µA (quiescent)

Ambient temperature

-20°C to +60°C

Dimensions L × W × H

93 × 94 × 23 (mm)

Colour

cream

Weight

110g

Approval

VdS G202140

Order number

249100

Order name

Monitor Module 1xSurv.In/Anal./200/SS M210E

Building Safety. Building Security.

A

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27

M210E_DBL_LST_EN_0804.PDF • PAGE 1

OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED

 