Detector Zone Extension
MGE8-1
•Extends fire detection control panels Series BC016 to 16 detector lines in addressable conventional technology
•Individual detector addressing with optional address module
•Individual setting of detector zone function
•Lines monitored for wire breakage, short circuit, and short to earth
Description
With the Detector Zone Extension
Depending on the type of detector (manual call point, automatic fi re detector with or without alarm verifi cati- on, fault message contacts as well as contacts for tech- nical messages), the function of the detector zone can be set separately for each detector line. Each input of the Detector Zone Extension is protected against over- voltage and thus provides high system stability.
Specifications
Current consumption at 24V | typ. 32mA (8 zones terminated, without detectors) |
Line voltage | typ. 20.0V |
Line current | typ. 3.8mA |
5.6kΩ or 3,3kΩ (depending on setup) | |
Line resistance | max. 50Ω per core |
Ambient temperature | |
Dimensions L × W × H | 100 × 65 × 15 (mm) |
Weight | 80g |
Part No. | 210110 |
Order name | Detector Zone Extension |