© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
NTM2408-1_DBL_LST_EN_0851.PDF • PAGE 2
ABuilding Safety. Building Security.
Power supply housings and accessories
The wall-mount cabinet NTG24-1 provides space
for the power supply module as well as for the in-
stallation of 2 stand-by batteries with 12V/max.
45Ah, one Relay Module RL58-1 or RL58-2 and
one Multi Module MEA244-1/E. In this case, the
power supply module serves as power supply
for the multi module and the loads that are ac-
tuated via the 4 outputs. Furthermore, via the
inputs of the multi module, fault messages can
be forwarded to the fi re detection control panel.
If required, further modules can be mounted in
the cabinet door.
Thanks to the sophisticated design of the Po-
wer Supply Front Panel NTG24-1CE, it can be
mounted either on a 19“ pivoting frame or on the
mounting plate of a switch cabinet. In both ca-
ses, the optional stand-by batteries are accom-
modated in the interior of the switch cabinet.
In addition to the power supply module, the Po-
wer Supply Front Panel NTG24-1CE can also ac-
commodate a Relay Module RL58-1 or RL58-2.
The Power Supply Housing NTG24-2 provides
space for the power supply module as well as
for the installation of 4 stand-by batteries with
12V/max. 85Ah, one Relay Module RL58-1 or
RL58-2 and one Multi Module MEA244-1/E.
The Battery Bracket BK24-1 is used for installing
stand-by batteries into the Power Supply Hou-
sing NTG24-2 or into a switch cabinet. The solid
sheet steel console can accommodate either
one battery with 12V/max. 85Ah or 2 batteries
with 12V/max. 45Ah.
Power Supply Housing NTG24-1
Protection class IP30
Dimensions W × H × D 442 × 460 × 203 (mm)
Colour grey white, RAL 9002
Weight without installations approx. 7kg
Order number 317030
Order name Power Supply Housing NTG24-1
Specifi cations
All housings are made of powder coated sheet steel. At
the front of the housing, the built-in display and opera-
ting board allows the signalling of the most important
operating conditions as well as the resetting of the in-
ternal buzzer.
The display and operating elements can be labelled in
the respective national language by means of the sup-
plied insertable labelling strips.