DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r
555-233-115 Issue 1
April 2000
Multicarrier G2 Universal Module to R8r EPN
5-40Standard Reliability
5
Set Additional Administration
1. Type list configuration software-version and press Enter to compare the
version number of the Release 8 software program ( displayed on the
terminal) with the TN786B version number (written on a lab el on the
TN786B’s faceplate). If the version numbers are not the same, c hange the
version number on the TN786B label so that they ag ree.
2. Type change system-parameters customer-options and press Enter.
Use this screen to enable the cus tomer’s right-to-use options on the
upgrade order. See

DEFINITY E nterprise Communications Server Release

8 Administrator’s Guide

, for details.
3. Type change site-data and press Enter. Use this screen to assign
system-specific infor mation (such as building , floor, stations, and so
forth).
4. Type save translation and press Enter. This instructs the system to write all
translation information from memory to the translation c ard.
!CAUTION:

If the terminal screen displ ays “translation corruption detected; c all

Lucent Technologies distributor immed iately”, an error was detected

in the translations. Call your Lucent Technologies representati ve.

Reconnect Cables to Upgraded EPN Cabinet
1. At the power distribu tion unit of the upgraded EPN, set the main circuit
brea ker t o OFF.
NOTE:
Powering down an EPN without powering down the PPN will set off
alarms. However, these alarms should c lear after power is restored
to each EPN.
2. Temporarily disconnect the lig htwave transceivers and fib er optic cab les
from the appropriate c arriers.
3. Replace the rear doors or rear p anels previously removed.
4. At the EPN cabinet, reconnect the lig htwave transceivers, fiber op tic
cables, and the c onnector cables.
5. Install the front door on the EPN cabinet if p reviously removed.