Side Wall Protection

STR/CVR Series Woodburning Fireplaces

Side Wall Protection

All joints (top, bottom and sides) where wall or deco- rative facing material meets fireplace surround must be completely sealed with a noncombustible material. (Figs. 20 and 24)

The special wall shield design described in Figure 20 is an alternate method of adding protection to side walls and can be used in place of the SP40 with the same wall clearances specified for the SP40. Rt must =1.85 minimum.

Examples of wall shield insulation:

1.Manville - CERAFORM 126, K=.27, 1/2 inches thick

2.CFM Corporation - EH2416, K = .458, 1 inch thick required.

Minimum Dimensions to Side Walls (for on-site contruction)

Model

 

STR33

STR36

STR42

CVR36

CVR42

Parallel Side Wall

A

44"

44"

44"

44"

44"

to Movable Doors

 

(1118 mm)

(1118 mm)

(1118 mm)

(1118 mm)

(1118 mm)

Perpendicular

B

16"

16"

20"

16"

20"

Side Wall to Firebox Opening

 

(406 mm)

(406 mm)

(508 mm)

(406 mm)

(508 mm)

Air Space to Sides

C

1/2"

1/2"

1/2"

1/2"

1/2"

or Back of Unit

 

(13 mm)

(13 mm)

(13 mm)

(13 mm)

(13 mm)

End Panel Parallel

D

--

--

--

36"

36"

to End of Unit

 

 

 

 

(914 mm)

(914 mm)

Perpendicular Side Wall

Perpendicular Side Wall

 

B B

C Manual backgroundManual backgroundManual backgroundManual backgroundManual background C

B Manual background

D Manual backgroundManual backgroundManual backgroundManual background C

Parallel Side Wall

A

 

 

 

Parallel Side Wall

A

STR Series

CVR Series

FP723

Fig. 23 Minimum firebox dimensions from combustible materials.

16

7412961

Page 16
Image 16
Majestic STR36, CVR42, STR42, STR33, CVR36 Side Wall Protection, STR/CVR Series Woodburning Fireplaces, B C C, B D C, 7412961