Installation Manual
1.5.1Electrical Ratings
Table
Rating, KVA/KW | 300/270 | 400/360 | 500/450 | 300/270 | 400/360 | 500/450 | |
Input voltage |
| 480VAC, 3PH, | 480VAC, 3PH, | 480VAC, 3PH, | 600VAC, 3PH, | 600,VAC,3PH, | 600VAC, 3PH, |
|
| 3W+G, 60hz. | 3W+G, 60hz. | 3W+G, 60hz. | 3W+G, 60hz. | 3W+G, 60hz. | 3W+G, 60hz. |
|
|
|
|
|
|
| |
Phase Rotation | ABC clockwise | ABC clockwise | ABC clockwise | ABC clockwise | ABC clockwise | ABC clockwise | |
|
|
|
|
|
|
| |
Input Current |
| 371 amps nominal, | 508 amps nominal, | 656 amps nominal, 322 amps nominal, | 441 amps nominal, | 569 amps nominal, | |
|
| 543 amps max. | 688 amps max. | 840 amps max. | 466 amps max. | 586 amps max. | 711 amps max. |
|
|
|
|
|
|
| |
Output Voltage | 480VAC, 3PH, | 480VAC, 3PH, | 480VAC, 3PH, | 600VAC, 3PH, | 600VAC, 3PH, | 600VAC, 3PH, | |
|
| 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. |
|
|
|
|
|
|
| |
Output Current | 361 amps | 481 amps | 601 amps | 289 amps | 385 amps | 481 amps | |
|
|
|
|
|
|
| |
Bypass voltage | 480 VAC, 3PH, | 480VAC, 3PH, | 480VAC, 3PH, | 600VAC, 3PH, | 600VAC, 3PH, | 600VAC, 3PH, | |
|
| 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. | 3or4W+G, 60hz. |
|
|
|
|
|
|
| |
Bypass Current | 361 amps | 481 amps | 601 amps | 289 amps | 385 amps | 481 amps | |
|
|
|
|
|
|
| |
DC Float Voltage | 545 VDC | 545 VDC | 545 VDC | 545 VDC | 545 VDC | 545 VDC | |
|
|
|
|
|
|
| |
DC Nominal Voltage | 480 VDC | 480 VDC | 480 VDC | 480 VDC | 480 VDC | 480 VDC | |
|
|
|
|
|
|
| |
DC | 390 VDC | 390 VDC | 390 VDC | 390 VDC | 390 VDC | 390 VDC | |
|
|
|
|
|
|
| |
DC Current (max) | 721 amps | 962 amps | 1195 amps | 721 amps | 962 amps | 1195 amps | |
|
|
|
|
|
|
|
|
Q1 Rating |
| 1000AT/1200AF | 1000AT/1200AF | 1000AT/1200AF | 1000AT/1200AF | 1000AT/1200AF | 1000AT/1200AF |
|
|
|
|
|
|
| |
Q4S, Q5N, SW | 800AT/1200AF | 800AT/1200AF | 800AT/1200AF | 700AT/1200AF | 700AT/1200AF | 700AT/1200AF | |
|
|
|
|
|
|
|
|
QF1 Rating |
| 700AT/1200AF | 1000AT/1200AF | 1200AT/1200AF | 700AT/1200AF | 1000AT/1200AF | 1200AT/1200AF |
|
|
| |||||
NOTE: | Information provided is for standard configurations; data may change with optional equipment. Consult |
|
the installation drawings provided with your equipment.
Introduction | page 1 — 5 |