EPS 7000 Single and Shared Systems
1.5.2 | Output |
|
| Power factor: | 0.9 lagging |
| Total harmonic distortion | < 2% (linear load) |
| (THD): | < 4% (for 100% |
| Transient regulation: | ± 1% for balanced load ± tbd for 100% unbalanced load |
| Transient response: | ± tbd for 100% step load change |
| Overload: | 125% of rated load for 10 minutes |
|
| 150% of rated load for 1 minute |
1.5.3 | Mechanical |
|
| Height: | 82 in/2083 mm |
| Depth: | 39 in/991 mm |
| Width: | See Table |
| Weight: | See Table |
| Finish: | MGE light gray |
1.5.4Environmental
Recommended environment: 20° to 25° C (68° to 77° F); 50% relative humidity; computer room or other temperature-
| and |
Operating temperature: | 0° to 40° C (32° to 86° F) except battery |
Storage: | |
Humidity: | up to 90% |
Altitude: | sea level to 1,000 meters (sea level to 3,280 feet) without derating; 1,000 to 2,000 |
| meters (3,280 to 6,560 feet): derate operating temperature to a maximum of 28° C |
| (82° F) |
page 1 — 6 | Introduction |