Installation Manual
3.2.3Installations with More Than 50,000 Amps Available Fault Current.
Where available fault current exceeds 50,000 amps, follow recommended cable restraints as shown in Figure
Figure
To Conduit End
B
A
6inches (152m)
A
6inches (152m)
POWER TERMINALS
!CAUTION: HAZARD OF CONDUCTOR MOVEMENT UNDER
Failure to observe these precautions can result in conductors pulling out of the lugs or damage to this equipment.
Wrap line cables together and secure cables using:
ANominal
12 inches (305mm) from the terminals with five wraps, and
Bevery additional 6 inches with five wraps or every 1 inch (25.4m) with one wrap.
IMPORTANT: Hazard of conductor movement under
Restrain customer bypass conductors where available fault currents exceeds 50,000 amps.
Installation | page 3 — 3 |