MGE UPS SYSTEMS
Pulsar ESV 8+/11+/14+/22+ EB 22/EB 22XLA :86-153277-00
12

connections

power connection of additional Pulsar
EB22and Pulsar EB22XLA:
check that the battery circuit breaker
20
on the rear of Pulsar EB22is flipped down
(position “O”),
connect the battery connection cord
19
(included with Pulsar EB22) between DC
connector
17
of Pulsar EB22and the DC
connector
16
of Pulsar ESV 22+,
if necessary, connect the battery connec-
tion cord(s)
19
between the DC connector
18
of Pulsar EB22and the DC connector
17
of the additional PulsarEB22XLA,
flip up (position “I”) the battery circuit
breaker
20
of Pulsar EB22,
use your computer cord 5to supply
Pulsar ESV 22+(utility power receptacle
4).
ESV22+ / EB22XLA / EB22preliminary checks
check that Pulsar ESV 22+is switched
off;if it is not, push the button 3" " on
the front, of the unit;
check that rating shown on identification
plate
10
corresponds to the input voltage
specification and power requirement of the
load.
Us/Out/Ausg
Imax3.4A
Ue/In/Eing
10A/250V
1
2
NetworkProtection
IN OUT
Current50Adc
VOLT 48Vdc
DCBREAKER
63A 65Vdc
<---PulsarESV22+ PulsarEB22XLA--->
Current50Adc
VOLT 48Vdc
Pulsar
ESV 22+
Pulsar
EB 22XLA
Pulsar
EB 22
10
4
519 19
16 17 18 1820 17