882108-YIM-B-1012
Johnson Controls Unitary Products 49
4. Shaded RPMs require Class II blower.
TABLE 31: FAN PERFORMANCE - 30 TON 1, 2
AIRFLOW (CFM) AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.2 0.4 0.6 0.8 1.0
RPM BHP3RPM BHP3RPM BHP3RPM BHP3RPM BHP3
6000 405 1.3 450 1.6 494 2.0 535 2.3 575 2.7
7000 444 1.9 485 2.3 524 2.7 562 3.0 599 3.4
8000 483 2.6 519 2.9 555 3.3 589 3.7 623 4.2
9000 520 3.5 554 3.9 586 4.3 618 4.7 649 5.2
10000 558 4.5 588 4.8 618 5.2 647 5.7 676 6.2
11000 603 5.7 629 6.2 656 6.7 683 7.2 709 7.7
12000 647 7.0 671 7.5 695 8.1 718 8.6 742 9.2
13000 687 8.9 709 9.3 731 9.9 753 10.4 776 10.9
14000 728 10.7 748 11.2 768 11.6 789 12.2 809 12.7
15000 767 12.7 786 13.2 805 13.8 825 14.4 845 15.0
AIRFLOW (CFM) AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.2 1.4 1.6 1.8 2.0
RPM BHP3RPM BHP3RPM BHP3RPM BHP3RPM BHP3
6000 612 3.1 649 3.5 683 3.9 717 4.3 748 4.7
7000 634 3.8 668 4.3 701 4.7 733 5.1 763 5.6
8000 655 4.6 687 5.1 719 5.5 749 6.0 779 6.5
9000 680 5.6 710 6.1 739 6.6 768 7.2 796 7.7
10000 704 6.7 732 7.2 760 7.7 787 8.3 813 8.9
11000 735 8.2 761 8.7 787 9.3 812 9.8 837 10.4
12000 766 9.7 790 10.3 814 10.8 837 11.4 861 12.0
13000 798 11.5 820 12.1 843 12.7 865 13.3 887 13.9
14000 830 13.3 851 13.9 872 14.6 893 15.2 914 15.9
15000 864 15.6 884 16.3 904 16.9 923 17.6 943 18.3
AIRFLOW (CFM) AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.2 2.4 2.6 2.8 3.0
RPM BHP3RPM BHP3RPM BHP3RPM BHP3RPM BHP3
6000 779 5.1 808 5.5 837 6.0 864 6.4 890 6.9
7000 793 6.1 822 6.6 850 7.0 877 7.5 903 8.1
8000 807 7.0 836 7.6 863 8.1 890 8.6 916 9.2
9000 823 8.3 850 8.8 877 9.4 902 10.0 928 10.6
10000 839 9.5 865 10.1 890 10.7 915 11.3 940 12.0
11000 862 11.0 886 11.6 910 12.2 934 12.9 957 13.5
12000 884 12.5 907 13.2 930 13.8 953 14.4 975 15.0
13000 909 14.6 931 15.2 953 15.9 975 16.5 996 17.2
14000 935 16.6 956 17.3 976 18.0 997 18.7 1017 19.4
15000 963 18.9 982 19.6 1002 20.4 1021 21.1 1040 21.8
AIRFLOW (CFM) AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.2 3.4 3.6 3.8 4.0
RPM BHP3RPM BHP3RPM BHP3RPM BHP3RPM BHP3
6000 916 7.4 940 7.9 964 8.3 988 8.8 1011 9.3
7000 928 8.6 953 9.1 977 9.6 1000 10.1 1023 10.7
8000 941 9.8 965 10.3 989 10.9 1013 11.5 1035 12.0
9000 952 11.2 976 11.8 1000 12.4 1023 13.0 1045 13.6
10000 964 12.6 987 13.2 1010 13.9 1033 14.5 1055 15.1
11000 981 14.1 1003 14.8 1025 15.5 1047 16.1 1069 16.8
12000 997 15.7 1019 16.4 1040 17.1 1061 17.8 1082 18.5
13000 1017 17.9 1038 18.6 1058 19.4 1078 20.1 1097 20.8
14000 1037 20.2 1056 20.9 1076 21.6 1094 22.4 1113 23.1
15000 1059 22.6 1078 23.3 1097 24.1 1115 24.9 1134 25.7
1. Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0 feet elevation.
2. Refer to Tables 57, 15, 21 and 33 for component additions and deductions to fan performance tables.
3. BHP includes drive losses.