2-5. Electrical Service Guide

 

 

340

 

 

440

 

 

 

 

 

 

 

 

Input Voltage

230

400

520

230

400

520

 

 

 

 

 

 

 

Input Amperes at Rated Output

55

32

25

79

46

25

 

 

 

 

 

 

 

Max Recommended Standard Fuse or Circuit

55

32

25

79

46

25

Breaker Rating in Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

** Input Conductor Size in mm2

6

6

6

6

6

6

** Grounding Conductor Size in mm2

6

6

6

6

6

6

** Power cord supplied with the unit is sized for 230V operation. Larger power cord may be required for cable lengths greater than 3 meters. C onsult national and local regulations.

2-6. Selecting a Location and Connecting Input Power

18 in (457 mm) for airflow

GND/PE

Connect First

1

OFF

ON

3060

100

160

1.6 220

2 2.54 5 Amp.

Have only qualified persons make this installation.

1 Rating Label

Supply correct input power.

GND/PE

L1 (U)

L2 (V)

L3 (W)

ST-801 721

OM-193 696 Page 7

Page 11
Image 11
Miller Electric 340, 440 manual Electrical Service Guide, Selecting a Location and Connecting Input Power