Frequency setting by analog input (t erminal 1, 2, 4)
Refer to the following table and set Pr. 73 and Pr. 267. ( indicates the main speed setting)
Set the voltage/current input switch referring to the table below.
AU
signal Terminal 4 Input Pr. 73
Setting
Terminal 2
Input
Terminal 1
Input
Compensation Input
Terminal and
Compensation Method
Polarity Reversible
OFF
00 to 10V 0 to ±10V
Terminal 1
Added compensation No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
1
(initial value) 0 to to 5V 0 to ±10V
20 to 10V 0 to ±5V
30 to 5V 0 to ±5V
4 0 to 10V 0 to ±10V Terminal 2
Override
5 0 to 5V 0 to ±5V
60 to 20mA 0 to ±10V
Terminal 1
Added compensation
70 to 20mA 0 to ±5V
10 0 to 10V 0 to ±10V
Yes
11 0 to 5V 0 to ±10V
12 0 to 10V 0 to ±5V
13 0 to 5V 0 to ±5V
14 0 to 10V 0 to ±10V Terminal 2
Override
15 0 to 5V 0 to ±5V
16 0 to 20mA 0 to ±10V Terminal 1
Added compensation
17 0 to 20mA 0 to ±5V
ON
Pr. 267 setting 0
0 to ±10V
Terminal 1
Added compensation No
(Indicates that a
frequency command
signal of negative
polarity is not
accepted.)
0
(initial
value)
4 to 20mA
1
(initial value) 0 to ±10V
20 to ±5V
30 to ±5V
4 0 to 10V Terminal 2
Override
11 to 5V *
5 0 to 5V
6
0 to ±10V
Terminal 1
Added compensation
70 to ±5V
10 0 to ±10V
Yes
11 0 to ±10V
22 to 10V *
12 0 to ±5V
13 0 to ±5V
14 0 to 10V Terminal 2
Override
15 0 to 5V
16 0 to ±10V Terminal 1
Added compensation
17 0 to ±5V
: Invalid
* If the input specification to terminal 4 is changed from the current input (Pr. 267 = "0") to the 0 to 5V or 0 to 10V voltage input (Pr. 267 ="1 or
2"), calibrate the input with C6. (Refer to page 177)
Terminal 2 Input
Specifications Pr. 73 Setting Switch 2 Terminal 4 Input
Specifications Pr. 267 Setting Switch 1
Voltage input (0 to 10V) 0, 2, 4, 10, 12, 14 OFF Voltage input (0 to 10V) 2 OFF
Voltage input (0 to 5V) 1 (initial value), 3, 5, 11, 13, 15 OFF Voltage input (0 to 5V) 1 OFF
Current input (0 to 20mA) 6, 7, 16, 17 ON Current input (0 to 20mA) 0 (initial value) ON
CAUTION
Turn the AU signal ON to make terminal 4 valid.
Match the setting of parameter and switch. A different setting may cause a fault, failure or malfunction.
The terminal 1 (frequency setting auxiliary input) signal is added to the main speed setting signal of the terminal 2 or 4.
When an override is selected, the terminal 1 or 4 is used for the main speed setting and the terminal 2 for the over ride signal
(50% to 150% at 0 to 5V or 0 to 10V). (When the main speed of the terminal 1 or terminal 4 is not input, compensation by the
terminal 2 is invalid.))
Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output frequency
command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down t o the acceleration/deceleration reference frequency, is not
affected by the change in Pr. 73 setting.
When Pr. 22 Stall prevention operation level = "9999", the value of the terminal 1 is as set to the stall prevention operation level.
( indicates an initial value.)