12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2102
[SP. UNIT LAY ERR.]
Seven or more A1SD51S have been installed.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Keep the number of A1SD51S to six or fewer.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)
2103
[SP. UNIT LAY ERR.]
•Two or more QI60/A1SI61 modules are mounted
in a single CPU system.
•Two or more QI60/A1SI61 modules are set to the
same control CPU in a multiple CPU system.
•Two or more A1SI61 modules are loaded in a
multiple CPU system.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
•Reduce the number of QI60/A1SI61 modules
mounted in the single CPU system to one.
•Change the number of QI60/A1SI61 modules set
to the same control CPU to only one in the
multiple CPU system.
•Reduce the number of A1SI61 modules to only
one in the multiple CPU system. When using an
interrupt module with each QCPU in a multiple
CPU system, replace it with the QI60. (Use one
A1SI61 module + max. three QI60 modules or
only the QI60 modules.)
Qn(H)*3
QnPH
[SP. UNIT LAY ERR.]
Two or more QI60, A1SI61 interrupt modules have
been mounted.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Install only 1 QI60, A1SI61 module. Qn(H)
QnPRH
[SP. UNIT LAY ERR.]
Two or more QI60 modules are mounted.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
Reduce the QI60 modules to one. Q00J/Q00/Q01*5
[SP. UNIT LAY ERR.]
Two or more QI60 modules where interrupt pointer
setting has not been made are mounted.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:–
■Diagnostic Timing
•At p ower ON/At reset
•Reduce the QI60 modules to one.
•Make interrupt pointer setting to the second QI60
module and later.
Q00J/Q00/Q01*3
QnU
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.
*5 The module whose first 5 digits of serial No. is "04101" or later.