12-23
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.4 Error code list (2000 to 2999)
2114
[SP. UNIT ERROR]
An instruction, which on execution specifies other
stations, has been used for specifying the host
CPU. (An instruction that does not allow the host
CPU to be specified).
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:Program error location
■Diagnostic Timing
•W hen instruction executed/ STOP RUN
Read the individual information of the error using
the GX Developer, check the program
corresponding that value (program error location),
and make correction.
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/Continue
Q00J/Q00/Q01*3
Qn(H)*3
QnPH
QnU
2115
[SP. UNIT ERROR]
An instruction, which on execution specifies the
host CPU, has been used for specifying other
CPUs. (An instruction that does not allow other
stations to be specified).
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:Program error location
■Diagnostic Timing
•W hen instruction executed/ STOP RUN
Q00J/Q00/Q01*3
Qn(H)*3
QnPH
2116
[SP. UNIT ERROR]
•An instruction that does not allow the under the
control of another CPU to be specified is being
used for a similar task.
•Instruction was executed for the A or QnA
module under control of another CPU.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:Program error location
■Diagnostic Timing
•W hen instruction executed/ STOP RUN
Q00J/Q00/
Q01*3
Qn(H)*3
QnPH
QnU
2117
[SP. UNIT ERROR]
A CPU module that cannot be specified in the
instruction dedicated to the multiple CPU system
was specified.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:Program error location
■Diagnostic Timing
•W hen instruction executed/ STOP RUN
2118
[SP. UNIT ERROR]
When the online module change setting is set to be
“enabled” in the PLC parameter in a multiple CPU
system, intelligent function module controlled by
other CPU using the FROM instruction/intelligent
function module device (U \ G) is specified.
■Collateral information
•Co mmon Information:Module No. (Slot No.)
•Individual Information:Program error location
■Diagnostic Timing
•W hen instruction executed
•When performing the online module change in a
multiple CPU system, correct the program so that
access will not be made to the intelligent function
module controlled by the other CPU.
•When accessing the intelligent function module
controlled by the other CPU in a multiple CPU
system, set the online module change setting to
be “disabled” by parameter.
Qn(H)*3
QnPH
QnU*7
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU
*3 The function version is B or later.
*7 The Universal model QCPU except the Q00UJCPU, Q00UCPU, Q01UCPU, and Q02UCPU.