
12-72
6102
[TRK. TRANS. ERR.]
A data sum value error occurred in tracking (data
reception).
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
•Common Information:–
•Individual Information:–
■Diagnostic Timing
•Always
•Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
•Confirm the redundant system startup procedure,
and execute a startup again.
RUN:
On
ERR.:
On
CPU Status:
Continue
QnPRH
6103
[TRK. TRANS. ERR.]
•A data error (other than sum value error)
occurred in tracking (data reception).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
•The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
•Common Information:–
•Individual Information:–
■Diagnostic Timing
•Always
6105
[TRK. TRANS. ERR.]
•An error (e.g. retry limit exceeded) occurred in
tracking (data transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
•The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
•Common Information:Tracking transmission data
classification
•Individual Information:–
■Diagnostic Timing
•Always
6106
[TRK. TRANS. ERR.]
•A timeout error occurred in tracking (data
transmission).
(This error may be caused by tracking cable
removal or other system power-off (including
reset).)
•The error occurred at a startup since the
redundant system startup procedure was not
followed.
(This can be detected from the control system or
standby system of the redundant system.)
■Collateral information
•Common Information:Tracking transmission data
classification
•Individual Information:–
■Diagnostic Timing
•Always
•Check the CPU module or tracking cable. If the
error still occurs, this indicates the CPU module
or tracking cable is faulty. (Contact your local
Mitsubishi representative, explaining a detailed
description of the problem.)
•Confirm the redundant system startup procedure,
and execute a startup again.
Error
Code
(SD0)
Error Contents and Cause Corrective Action LED Status
CPU Status
Corresponding
CPU